SPYDER MODEL 5 ENGINEERING TOOL
–
USER GUIDE
93
31-00282ES-01
3.
To swap-in the devices, right-click on the IRM
Config
folder in the tree, then click
Actions
, and then click
Swap In
in
the context menu
RESULT: The devices are swapped in. The successful swap-in is displayed in
Irm Operations Monitor.
Master Sync
The
“
Master Sync
”
function is based on a group of multiple devices that must have the same application type. This is
called a master sync group. The master sync group
is established via the “Clone Application” function
which clones the
application of one selected device (template) to multiple devices.
Among all devices, one device is defined as the source and the other devices are defined as targets. Then the master
sync command allows rolling out the current application (changes) of the source device to all target devices per one
step.
The master sync function works in online and offline mode on project level, but not in the devices. Hence, the
applications in the project do not have to be synchronous with the applications in the devices when working in teaching
mode ´on demand`.
Fig. 12.
Master Sync Group including Source and Target Devices
NOTE: Cloning of the application and the source-target definition for the devices can be done independently. That is, the
source-target definition of the devices can be done before or after cloning of the device application and vice versa.