SPYDER MODEL 7 VAV CONTROLLER INSTALLATION INSTRUCTIONS
31-00475-01
34
APPENDIX
Sensor Input Accuracy
The controller's internal sensor inputs support both 10 K NTC
Ω
and 20 K NTC
Ω
sensors. The following table lists
the typical minimum accuracies of the hardware and software for these temperature sensors.
NOTE:
This is the accuracy of the internal sensor input (ha software [linearization]) only. This table does not
include the characteristics of the sensors themselves, see
Sensor Characteristics on page 36
.
Table 29 Sensor Accuracies
Range
Measurement Error (Excluding Sensor Characteristics)
10 k
Ω
NTC
a)
20 k NTC
PT3000
NI1000TK5000
b)
-58 °F to -4 °F (-50 °C to -20 °C)
≤ 5.0 K
≤ 5.0 K
≤ 1.2 K
≤ 1.2 K
-4 °F to +32 °F (-20 °C to 0 °C)
≤ 1.0 K
≤ 1.0 K
≤ 0.7 K
≤ 0.7 K
32 °F to 86 °F (0 °C to 30 °C)
≤ 0.5 K
≤ 0.3 K
≤ 0.5 K
≤ 0.5 K
86 °F to 158 °F (30 °C to 70 °C)
≤ 0.5 K
≤ 0.5 K
≤ 0.7 K
≤ 0.7 K
158 °F to 212 °F (70 °C to 100 °C)
≤ 1.0 K
≤ 1.0 K
≤ 1.2 K
≤ 1.2 K
212 °F to 266 °F (100 °C to 130 °C)
--
≤ 3.0 K
≤ 1.2 K
≤ 1.2 K
266 °F to 302 °F (130 °C to 150 °C)
--
≤ 5.5 K
≤ 1.2 K
--
302 °F to 752 °F (150 °C to 400 °C)
--
--
--
--
a)
10 k NTC
Ω
specified for -22 °F to 212 °F (-30 °C to +100 °C) only.
b)
NI1000TK5000 specified for -22 °F to +266 °F (-30 °C to +130 °C) only.