ST7009A,B,C,D ELECTRONIC PROGRAMMABLE TIMER

68-3003

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not include
normal manufacturing tolerances; therefore, an individual
unit may not exactly match the listed specifications. Also, this
product is tested and calibrated under closely controlled
conditions, and some minor differences in performance can
be expected if those conditions are changed.

Models:

Channels:

ST7009A,C: 1.
ST7009B,D: 2.

Programs:
42 per day.

Holiday Program:
Yes.

Reserve Carryover (Minimum):
2 weeks.

Daylight Savings Time Key:
Yes.

Power Input:

ST7009A,B: 24V, 50/60 Hz.
ST7009C,D: 120V, 50/60 Hz.

Power Consumption:
4 VA.

Output:

ST7009A,C: 1 spdt relay.
ST7009B,D: 2 spdt relays.

Mounting:

ST7009A,C: Surface or DIN Rail.
ST7009B,D: Panel or Surface.

Switching Capacity:

16A resistive at 277 Vac.
1000W tungsten at 240 Vac.
1/2 hp at 120 Vac; 1 hp at 240 Vac.

Shortest Switching Time:
1 minute.

Accuracy:
+ 4 minutes per yr.

Ambient Temperature:
-20

°

F (-28

°

C) to 140

°

F (60

°

C).

Ambient Humidity:
0 to 95% RH, non-condensing.

LCD Time Display:
Selectable AM/PM or 24-hour.

Manual 3-way Override:

Temporary or permanent on or off.
LCD status indication display.

Contact Material:
Silver cadmium oxide.

Dimensions:
See Fig. 1.

2-1/8 (54)

3 (76)

2 (51)

2-1/16 (52)

3-1/4

(83)

DIN RAIL
MOUNTING

M12192

ST7009A,C

OS Number

Type

Input Voltage

Channels

Relay Output

Battery Reserve

ST7009A1003

24-hour, 7-day

24V, 50/60 Hz

1

1 spdt

7-day

ST7009B1002

24-hour, 7-day

24V, 50/60 Hz

2

2 spdt

7-day

ST7009C1001

24-hour, 7-day

120V, 50/60 Hz

1

1 spdt

7-day

ST7009D1000

24-hour, 7-day

120V, 50/60 Hz

2

2 spdt

7-day

Fig. 1. ST7009A,C, ST7009B,D dimensions in in. (mm) (1 of 2).

Summary of Contents for ST7009A

Page 1: ...Universal 24 hour or 7 day programming accurate to the second UL and CUL recognized components Multiple on off daily programs with unlimited flexibility Program simplicity with a minimal number of keys and program steps Holiday programming Built in program backup Daylight Savings Time changeover in the spring and fall Screw wiring terminals All models feature large keys and a large LCD display for...

Page 2: ...ST7009A C Surface or DIN Rail ST7009B D Panel or Surface Switching Capacity 16A resistive at 277 Vac 1000W tungsten at 240 Vac 1 2 hp at 120 Vac 1 hp at 240 Vac Shortest Switching Time 1 minute Accuracy 4 minutes per yr Ambient Temperature 20 F 28 C to 140 F 60 C Ambient Humidity 0 to 95 RH non condensing LCD Time Display Selectable AM PM or 24 hour Manual 3 way Override Temporary or permanent on ...

Page 3: ...y once A 4 is displayed under Th Enter the date for Summer Daylight Savings Time changeover for the current year by entering the date with the m key and the month with the h key If in military time set the date with the h key and the month with the m key Example April 7 is displayed as 04 07 if in AM PM time or 07 04 in military time G Press the 1h key once A 5 is displayed under Fr Enter the date...

Page 4: ... the Sel key is held down the numbers scroll up rapidly to 99 and then start over with 01 D Press the key to store the program The holiday symbol is displayed E To review or change the Holiday Program press the key To cancel the Holiday Program press the key a second time On the day the Holiday Program begins the Eighth Day Program is implemented at 12 00 AM Midnight taking priority over the regul...