S9103A ELECTRONIC FAN TIMER

5

69-0771B

ST9103 Operating Sequence (Continued).

Action

System Response

Thermostat ends call for fan.
(G terminal is de-energized.)

Circulating fan is de-energized.

Limit switch string opens.

Oil primary control shuts off burner.

Circulating fan is energized immediately at heat speed.

ST9103A opens oil primary control T-T connections.

Circulating fan runs as long as limit string stays open.

If there is a call for cooling or fan, the circulating fan switches from heat
speed to cool speed.

Limit switch string closes.

ST9103A begins heat fan off delay sequence.

Circulating fan turns off after the selected heat fan off delay timing.

ST9103A recloses oil primary control T-T connections.

Oil primary control is energized, initiating burner light off.

Continuous circulating fan is connected.
(Optional connectors are available for
separate circulating fan speed tap.)

Circulating fan is energized at low speed when there is no call for heat,  
cool or fan.

If fan operation is required by a call for heat, cool or fan, the ST9103A
switches off the continuous fan speed tap before energizing the other  
fan speed.

Electronic air cleaner is connected.
(Optional connectors are available for 120
Vac electronic air cleaner.)

Electronic air cleaner (EAC) connections are energized when the heat or
cool speed of the circulating fan is energized. EAC connections are not
energized when the optional continuous fan terminal is energized.

Humidity control is connected.
(Optional connectors are available for 120
Vac humidifier.)

Humidifier connections are energized when burner motor is energized.

Summary of Contents for ST9103A

Page 1: ...1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings and specifications given in the Instructions and on the product to assure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out the product operation as provided in these...

Page 2: ...1 C O O L C O N T E A C B U R N E R UNUSED MOTOR 1 2 3 4 5 6 7 BURNER MOTOR ST9103 L1 L2 ORANGE T1 T2 BLACK WHITE R8991 OIL PRIMARY CONTROL FLAME DETECTOR CAD CELL 1 INTERLOCK FUSE LIMIT CONTROL H E A T 3 1 2 1 DENOTES STANDARD TERMINAL DENOTES OPTIONAL TERMINAL 1 L2 N L1 H TO 120 VAC POWER SUPPLY H U M NOTE DENOTES LINE VOLTAGE CONNECTIONS DENOTES LOW VOLTAGE CONNECTIONS ...

Page 3: ... CIRCUIT BOARD WIRING M5552 ELECTRONIC AIR CLEANER OPTIONAL TO 120 VAC POWER SUPPLY R8991 LIMIT SENSOR CIRCULATION BLOWER K1 K2 R8991 CONTROL K3 MED HIGH LOW FUSE INTERLOCK S2 N3 K2 HEAT K1 CONSTANT MED HIGH N1 LIMIT CN6 1 1 CN6 2 CN6 4 L1 L2 CN6 7 T1 T2 R8891 CN6 6 CN6 3 X 24 VAC 120 VAC S1 BURNER MOTOR HUMIDIFIER OPTIONAL ACCESSORY OPTIONAL S3 CN6 8 CN6 5 N7 N4 N6 HUM 1 DENOTES OPTIONAL CONNECTI...

Page 4: ...y timing begins When timing is complete the circulating fan is de energized ST9103A returns to standby mode oil primary control and circulating fan are off Burner fails to light Oil primary control locks out within lockout timing timing depends on oil primary control Burner motor is de energized If heat fan has started it continues through the selected delay off period Established flame fails Burn...

Page 5: ... connections Oil primary control is energized initiating burner light off Continuous circulating fan is connected Optional connectors are available for separate circulating fan speed tap Circulating fan is energized at low speed when there is no call for heat cool or fan If fan operation is required by a call for heat cool or fan the ST9103A switches off the continuous fan speed tap before energiz...

Page 6: ...97 Printed in U S A Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Helping You Control Your World ...

Page 7: ... Avant d installer ce produit 1 Bien lire les instructions Ne pas les suivre pourrait endommager le produit et constituer un danger 2 Vérifier les caractéristiques spécifiées dans la fiche technique et sur le produit afin de s assurer que le produit convient à l application choisie 3 L installateur doit être un technicien d expérience ayant reçu la formation appropriée 4 Une fois l installation te...

Page 8: ...9103 L1 L2 ORANGE T1 T2 NOIR BLANC RÉGULATEUR PRIMAIRE DE MAZOUT R8991 DÉTECTEUR DE FLAMME CELLULE AU CADMIUM 1 VERROUILLAGE FUSIBLE INTERRUPTEUR DE FIN DE COURSE 3 1 2 1 BORNE STANDARD BORNE FACULTATIVE 1 L2 N L1 H H U M NOTE RACCORDEMENT TENSION SECTEUR RACCORDEMENT BASSE TENSION BASSE MOYENNE BASSE MOYENNE ÉLEVÉE ÉLEVÉE 120 V C A 24 V C A SOUS TENSION NEUTRE VERS ALIMENTATION 120 V C A INUTILIS...

Page 9: ...TEUR DU LIMITEUR R8991 VENTILATEUR DE CIRCULATION D AIR K1 K2 R8991 CONTROL K3 MOYENNE ÉLEVÉE BASSE FUSIBLE VERROUILLAGE S2 N3 K2 CHAUFFAGE K1 CONTINUE MOYENNE ÉLEVÉE N1 INTERRUPTEUR DE FIN DE COURSE CN6 1 1 CN6 2 CN6 4 L1 L2 CN6 7 T1 T2 R8891 CN6 6 CN6 3 X 24 V C A 120 V C A S1 MOTEUR DU BRÛLEUR HUMIDIFICATEUR FACULTATIF ACCESSOIRE FACULTATIF S3 CN6 8 CN6 5 N7 N4 N6 HUM 1 CONNEXIONS COMPOSANTS ET...

Page 10: ...ation le ventilateur de circulation d air est sous tension et l air chaud circule dans les pièces Fin de la commande de l appel de chaleur du thermostat Borne W hors tension Le régulateur primaire est hors tension et met fin au cycle de chauffage La temporisation d arrêt du ventilateur de chauffage commence À la fin de la temporisation le ventilateur de circulation d air est hors tension Le ST9103...

Page 11: ... ou de ventilation le ventilateur de circulation passe du régime de chauffage à celui de refroidissement Le câble de l interrupteur de fin de course se ferme Le ST9103A commande le début de la temporisation d arrêt du ventilateur de chauffage À la fin de la temporisation choisie le ventilateur de circulation s arrête Le ST9103A referme les contacts T T du régulateur primaire Le régulateur primaire...

Page 12: ...B G H 3 97 Imprimé aux États Unis Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Pour la ma trise de votre univers ...

Reviews: