Revision 3
STT850
Temperature Transmitter User’s Manual
Page 45
Figure 15
– Locating the Failsafe and Write Protect Jumpers
Table 13
– HART and DE Failsafe and Write Protect Jumpers
Jumper
Arrangements
Description
Failsafe = UP (High)
Write Protect = OFF (Not Protected)
Failsafe = DOWN (Low)
Write Protect = OFF (Not Protected)
Failsafe = UP (High)
Write Protect = ON (Protected)
Failsafe = Down (Low)
Write Protect = On (Protected)
1.
Turn OFF Transmitter power (Power removal is only required in accordance with
area safety approvals. Power removal is only required in Class 1 Div 1
Explosionproof and Class 1 Div 2 environments).
2.
Loosen the end cap lock, and unscrew the end cap from the electronics side of the
Transmitter housing.
3.
If equipped with a Display module, carefully depress the two tabs on the sides of the
Display Module, and pull it off.