Figure 5-2 Control Unit Printed Circuit Board
Use the tables below to determine the operating status of the protective safety equipment. To use the acoustic signal to
determine the protective safety equipment status, the buzzer switch must be set to the ON position (see figure above).
Table 5-2 FF-LS Status in Automatic Restart Mode (with power ON)
Beam Condition
LED And Buzzer Status
FF-LS Status and Remedy
CLEAR
•
Red LEDs 5 and 7 flicker.
•
Yellow LEDs 4 and 6 are always illuminated.
•
Acoustic signal NOT present. (1)
•
The FF-LS is operating correctly.
•
Safety output contacts X1 and X2 are closed.
INTERRUPTED
•
Red LEDs 5 and 7 flicker.
•
Yellow LEDs 4 and 6 are NOT illuminated.
•
Acoustic signal present (short interval). (1)
•
The FF-LS is operating correctly, but needs a
clear beam status.
•
Safety output contacts X1 and X2 are open.
(1) Buzzer switch ON.
Table 5-3 FF-LS Status in Start and Restart Interlock (Manual) Mode
Beam Condition
LED And Buzzer Status
FF-LS Status and Remedy
AT POWER UP
CLEAR
•
Red LEDs 5 and 7 are always illuminated.
•
Yellow LEDs 4 and 6 are NOT illuminated.
•
Acoustic signal is always present. (1)
•
The FF-LS is operating correctly but needs to
be restarted.
•
Safety output contacts X1 and X2 are open.
INTERRUPTED
•
Red LEDs 5 and 7 are always illuminated.
•
Yellow LEDs 4 and 6 are NOT illuminated.
•
Acoustic signal is always present. (1)
•
An object within the sensing field forbids the
effective restart of the FF-LS.
•
Safety output contacts X1 and X2 are open.
DURING NORMAL OPERATION
CLEAR
•
Red LEDs 5 and 7 are illuminated.
•
Yellow LEDs 4 and 6 are always illuminated.
•
Acoustic signal NOT present. (1)
•
The FF-LS is operating correctly.
•
Safety output contacts X1 and X2 are closed.
INTERRUPTED
THEN RELEASED
•
Red LEDs 5 and 7 are always illuminated.
•
Yellow LEDs 4 and 6 are NOT illuminated.
•
Acoustic signal always present. (1)
•
The FF-LS is operating correctly but needs to
be restarted.
•
Safety output contacts X1 and X2 are open.
(1) Buzzer switch ON.
5.3
Troubleshooting
POWER APPLIED TO MACHINE CONTROL SYSTEM
Before intervention, turn off and disconnect power from FF-LS Series safety light curtain and machine.
Failure to comply with these instructions could result in death or serious injury.
Terminals
Output contact fuses
LED indicators
(supply voltage)
LED Indicators
(system condition)
Function
Summary of Contents for SYA14 Series
Page 2: ...2 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 6: ...6 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 26: ...26 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 62: ...62 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 70: ...70 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 76: ...76 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 78: ...78 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 79: ...107031 23 EN FR26 GLO 1199 Printed in France 79 8 CE Declaration of Conformity ...
Page 80: ...80 107031 23 EN FR26 GLO 1199 Printed in France This page has been left intentionally blank ...
Page 84: ......
Page 158: ......
Page 160: ......
Page 161: ...For application help call 1 800 537 6945 Honeywell MICRO SWITCH Sensing and Control 80 ...
Page 165: ...3 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 201: ...39 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 205: ...43 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 207: ...45 107022 14 EN FR26 GLO 0100 Printed in Germany This page has been left intentionally blank ...
Page 208: ...107022 14 EN FR26 GLO 0100 Printed in Germany 46 9 Declaration of Conformity ...
Page 219: ...11 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 229: ...21 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 257: ...49 107006 11 EN FR26 GLO 0300 Printed in Germany This page has been left intentionally blank ...
Page 260: ...107006 11 EN FR26 GLO 0300 Printed in Germany 52 9 3 Declaration of conformity ...
Page 340: ...Safety Perimeter Guarding Installation Manual FF SPS4 Series Safety Perimeter Guarding ...
Page 536: ...2 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 538: ...4 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 542: ...107004 15 EN FR26 ROW 0899 Printed in France 8 This page has been left intentionally blank ...
Page 620: ...86 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 624: ...90 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 626: ...92 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...
Page 627: ...107004 15 EN FR26 ROW 0899 Printed in France 93 8 CE Declaration of Conformity ...
Page 628: ...94 107004 15 EN FR26 ROW 0899 Printed in France This page has been left intentionally blank ...