background image

95C-10903-1

T451, T651 MOTOR-RATED PRECISION THERMOSTATS

SPECIFICATIONS • ORDER INFORMATION

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or your distributor, refer to the 
TRADELINE catalog or price sheets for complete ordering number, or specify:

1. Model
2. Electrical load(s)
3. Accessories.

If you have additional questions, need further information, or would like to comment on our products or services, please write 
or phone:

1.  Your local Honeywell Home and Building Control Sales Office (check white pages or phone directory).
2.  Home and Building Control Customer Satisfaction

Honeywell Inc., 1885 Douglas Drive North.
Minneapolis, MN 55422 (612) 951-1000

3.  In Canada — Honeywell Limited, 35 Dynamic Drive, Toronto, ON  M1V 4Z9, 1-800-405-9835.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

Important:  The specifications given in this publication do 

not include normal manufacturing tolerances. Therefore this
unit may not exactly match the listed specifications . This 
product is tested and calibrated under closely controlled 
conditions, and some minor differences in performance can
be expected if these conditions are changed.

Models:

T451A SPST and T451B DPST (with positive off) for 
heating only.
T651A SPDT for heating/cooling.

Control Range:

44 - 86°F (7 - 28°C) for models T451A, T651A.
50 - 86°F (10 - 28°C) for model T451B.

Sensing Element: Vapor-filled dual diaphragm.

Differential: 2°F (1°C) 

Droop: 2°F @ mid load range.

Barometer Sensitivity: 1/8°F/”wc (0.3°C/kPa).

Thermometer: 50 - 90°F (10 - 30°C) in 10°F (5°C) increments. 

Electrical Ratings:

50/60Hz

120 V

208V

240V

277V

Full Load

9.8A

5.6A

4.9A

4.2A

Locked Rotor

58.8A

33.6A

29.4A

25.2A

Pilot Duty 

125 VA

Resistive 

22A Non Inductive        19ANI

Heating Only

2.5kW    4.5kW            5kW        

Finish: Classic beige-and-light gold standard. 

White models available.

Mounting:

Mounts directly on vertical, single-gang NEMA Standard 
(2” x 4”) electrical box.

Wiring Connections:

6” (150 mm) leadwires suitable for connecting to aluminum
conductors wiring if used with approved special service 
CO/ALR solderless wire connectors. Leadwires color-
coded red for heating, blue for cooling, black for common.

Approvals:

Canadian Standards Association Certified; File No. LR1322
Performance Certified for electric heating per C273.4A.
UL file E47434.

Accessories:

272804A Range stops and cover locking assembly 

(included in selected models only).

220213  Wallplate, covers old T451/T651 (1000 series) 

wall marks.

TG511   Thermostat guard for security and protection.

Fig. 1 — Dimensions of T451, T651 in inches (mm):

2

Summary of Contents for T451

Page 1: ...CH mechanism rated 1 2 hp inductive 5 kW resistive Vertical mounting on 2 x 4 NEMA standard single gang outlet box High sensitivity vapor filled stainless steel dual diaphragm sensing element Engineering plastic base to isolate sensor from switch heat and minimize droop CSA Certified UL Listed Altitude compensation 44 F 7 C frost protection setting for heating application independent of calibratio...

Page 2: ...d some minor differences in performance can be expected if these conditions are changed Models T451A SPST and T451B DPST with positive off for heating only T651A SPDT for heating cooling Control Range 44 86 F 7 28 C for models T451A T651A 50 86 F 10 28 C for model T451B Sensing Element Vapor filled dual diaphragm Differential 2 F 1 C Droop 2 F mid load range Barometer Sensitivity 1 8 F wc 0 3 C kP...

Page 3: ...ay not be used as a disconnect switch 3 Leave cover on the thermostat while making wiring connections Use solderless connectors approved for the type number and gauge of wires being joined Connect as per Fig 2 for the appropriate application Fig 2 Wiring connections 4 Pre bend and push leadwires into the electrical junction box 5 Hold the thermostat base with one hand and remove the thermostat cov...

Page 4: ...removed setpoint knob clockwise by the amount of temperature error Each mark on the triangular arm represents 2 F 1 C of adjustment Snap the knob back onto the setpoint cam Fig 4 Recalibrating Thermostat Fig 5 Installing Range Stops Insert pins into temperature stop positions Security Features Range Stops 1 Set thermostat to desired setpoint Remove cover 2 Install plastic dowels supplied or purcha...

Reviews: