background image

T7100D,E,F MICROELECTRONIC COMMERCIAL THERMOSTATS AND Q7100A,C,D SUBBASES

68-0163—3

13

Minimum-Off Timing

A minimum-off timer assures that the cooling compressor or
heat pump compressor does not come on again for at least
five minutes after it turns off. The minimum-off timer is
triggered when the compressor goes off and when the system
switch is changed. If the compressor turns off when the
setpoint is changed, then the minimum-off timer is triggered.
The minimum-off timer operates during the first stage of both
heating and cooling on the heat pump thermostat models and
during cooling only on the standard application models.

Emergency Heat (select models)

When the system is set for Emergency Heat, the auxiliary
heat is stage one and the compressor stages are locked off.
Depending on the model, the fan can be activated when
Emergency Heat is used.

Fan Control

The fan is on when these conditions are present (it can take
up to 20 seconds for the fan to turn on):

Fan On:

The fan is energized continuously.

Fan Auto:

The fan runs only with the heating and cooling
system.

Select models allow the installer the option of electric or
conventional heat fan operation in the Installer Setup. When
set for electric heat systems, the fan comes on at the same
time as the heat when energized by the thermostat. The fan is
energized by the plenum switch when set for conventional
heating system.

Override Temperature (select models)

The T7100 temperature settings can be overridden when using
the Override key, a remote setback timer, or a occupancy sensor.
When using the override feature, the temperature settings
change according to the Installer Setup 27 setting.

When the Override key (select T7100F models)  is pressed,
the thermostat temporarily changes from the comfort setpoint
to the temporary setpoint by the amount set in Installer Setup
27. See Table 11. Pressing the key a second time cancels the
temporary setting.

The normal contact state (comfort setpoint) when using a
remote timer or occupancy sensor is closed. The temporary
contact state (temporary setpoint) is open.

NOTE:

Pressing the Override key at any time changes the
state of the contacts.

Table 11. Examples of Temperature Overrides.

Always check the display to determine if the thermostat is
controlling to the comfort, temporary or remote setpoint.
Temporary is displayed when the thermostat is operating at
the temporary setpoint.

System

Setting

Comfort
Setpoint

Installer Setup 27

Setting

Temporary

Setpoint

Heat

68°F

10°F

58°F

Cool

74°F

10°F

84°F

WIRING DIAGRAMS (FIG. 17-22)

Fig. 17. Typical hookup of Q7100A1044 in a one-stage

heat and one-stage cool conventional system.

Fig. 18. Typical hookup of Q7100C1024 in a one-stage

heat and one-stage cool heat pump system.

POWER SUPPLY.  PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

1

1

L1
(HOT)

L2

M4831A

HEAT 
RELAY OR 
VALVE COIL

COMPRESSOR
CONTACTOR

RC

O

G

X

W

COOL 
DAMPER

SUBBASE

B

HEAT
DAMPER

Y

FAN 
RELAY

RH

L1
(HOT)

L2

POWER SUPPLY.  PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

1

M4833A

COMPRESSOR
CONTACTOR

FAN
RELAY

R

O

W

X

Y

X1

COOL
CHANGEOVER
VALVE

SUBBASE

1

B

HEAT
CHANGEOVER
VALVE

G

HEAT 
RELAY

EQUIPMENT
MONITOR

Summary of Contents for T7100D

Page 1: ...m off time for cooling compressor and heat pumps Field configurable select models for F or C temperature display automatic or manual changeover electric or conventional heat fan operation Up to two light emitting diodes LEDs for easy reference Remote temperature sensor and setback timer capability select models System test simplifies troubleshooting Contents Application 1 Features 1 Specifications...

Page 2: ...00 Models See Table 1 Table 1 T7100 Thermostat Models aDepends on the model Q7100 Models See Table 2 Table 2 Q7100 Subbase Models aDepends on the model Electrical Rating Input Power 18 to 30 Vac 50 60 Hz Load Rating See Table 3 Table 3 Maximum Amperes at 18 to 30 Vac Relay Running A Inrush A Heat 02 to 1 5 3 5 at 200 000 cycles Cool 02 to 1 5 7 5 at 100 000 cycles Fan Reversing Valve Emergency Hea...

Page 3: ...lation Location Subbase Without Remote Mounted Temperature Sensor Install the subbase about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 2 Do not install the subbase where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncoole...

Page 4: ...T7100 Q7100 Thermostat Subbase Fig 7 Nine T7047C Sensors providing temperature averaging network for T7100 Q7100 Thermostat Subbase Subbase Installation The subbase can be mounted horizontally on the wall or on a 2 in x 4 in wiring box 1 Position and level the subbase for appearance only The thermostat functions properly even when not level 2 Use a pencil to mark the mounting holes See Fig 8 3 Rem...

Page 5: ...OUNTING HOLES MOUNTING SCREWS M6531 WALL ANCHORS 2 Fig 9 Proper wiring technique Table 4 Terminal Designations and Descriptions M4826 FOR WRAPAROUND INSERTION STRIP 7 16 IN 11 MM FOR STRAIGHT INSERTION STRIP 5 16 IN 8 MM Standard Terminal Designations Typical Connection Function Terminal Type B Heating changeover valve or damper Output 24V powered contact D D Remote setback timer Input Dry contact...

Page 6: ...uto Equipment controls fan The system default setting is Heat and the fan default setting is Auto Use the keys to change to the desired settings See Fig 11 NOTE Always press the keys with your fingertip or similar blunt tool Sharp instruments like a pen or pencil point can damage the keyboard Temperature Settings The default setpoint for heat is 70 F 21 C and for cool is 78 F 25 5 C Press the incr...

Page 7: ... Fig 13 LCD display of all segments Fig 12 Set Installer Setup lockout DIP switch 1 on back of thermostat INSTALLER SETUP NOTE For most applications the thermostat factory settings do not need to be changed Review the factory settings in Table 6 and if no changes are necessary go to the Installer System Test section The Installer Setup is used to customize the thermostat to specific systems Instal...

Page 8: ...ms 08 8 cph factory setting for conventional systems 09 9 cph used for electric heat systems Output stages of cooling T7100F only 08 02 Two stages of cool 00 or 01 00 No cooling 01 One stage cooling Cooling cycle rate T7100F only 09 04 Stage 1 at 4 cph 03 03 3 cph 10 04 Stage 2 at 4 cph Changeover T7100F only 12 00 System setting key is operational 01 or 02 01 Heat Cool Off no Auto 02 Auto only De...

Page 9: ...3 04 4 minute minimum off time for the compressor 00 01 02 03 or 05 Minimum number of minutes 0 thru 5 the compressor is off between calls for the compressor Temperature range stops in heating T7100F only 34 90 Highest heating setpoint allowed 40 89 Temperature range 1 F increments for heating setpoint Temperature range stops in cooling T7100F only 35 45 Lowest cooling setpoint allowed 46 99 Tempe...

Page 10: ...NOTE Press and hold the increase and decrease keys together for three seconds to exit the Self Test The Self Test times out after five minutes without any key presses Thermostat Information 1 Press the Information i key to access the thermostat information M6792A TEST NUMBER Test Number Self Test Description 10 19 Heating equipment can be turned on and off 20 29 Emergency heat Q7100C only equipmen...

Page 11: ...stem fan remain on 13 Stage three heat turns on Stage one and stage two heat remain on 12 Stage three heat turns off 11 Stage two heat turns off 10 Stage one heat and system fan turn off Emergency Heating Equipment Self Test with select models of Q7100C subbase i 20 Change from heating to emergency heating equipment Self Test 21 Emergency heat turns on System fan also turns on 20 Emergency heat tu...

Page 12: ...tly before the room temperature reaches the setpoint to keep the heat remaining in the ductwork from overheating the room In severe weather a conventional control with a heat anticipator tends to turn off the system too soon so the effective setpoint is somewhat below the setpoint In very cold weather the difference between setpoint and effective control point can be 5 F or 6 F 2 C or 3 C with a c...

Page 13: ... when using the Override key a remote setback timer or a occupancy sensor When using the override feature the temperature settings change according to the Installer Setup 27 setting When the Override key select T7100F models is pressed the thermostat temporarily changes from the comfort setpoint to the temporary setpoint by the amount set in Installer Setup 27 See Table 11 Pressing the key a secon...

Page 14: ...TO THE D TERMINAL DO NOT PARALLEL SEVERAL THERMOSTATS FROM A SINGLE SOURCE UNLESS ISOLATION RELAYS ARE USED POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED EM HT RELAY DOES NOT CYCLE TO TURN OFF THE EM HEAT GO TO SYSTEM SELECTION AND CHOOSE HEAT IF O B INPUT IS REQUIRED JUMPER W1 TO Y 1 M15324B COMPRESSOR CONTRACTOR FAN RELAY D O G Y X1 COOL CHANGEOVER VALVE HEAT CHANGEOV...

Page 15: ...s in the Off position if so set to the On position Check wiring between thermostat and HVAC equipment and replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Temperature display is incorrect Room temperature display has been reconfigured Enter Installer Setup 37 and reconfigure the display Thermostat is configured for F or C display Enter In...

Page 16: ...oes not come on No power to the thermostat Check that X terminal is connected to the system transformer Check for 24 Vac between X and R or RC and Y terminals If missing 24 Vac Check if the circuit breaker is tripped if so reset the circuit breaker Check if the system fuse is blown if so replace the fuse Check if the system switch at the equipment is in the Off position if so set to the On positio...

Reviews: