T7100D,E,F MICROELECTRONIC COMMERCIAL THERMOSTATS AND Q7100A,C,D SUBBASES
68-0163—3
8
Mode
Number
(Press
i
key
Factory-Setting
Other Choices
(Press
▲
or
▼
key to change)
Actual
Select
to change)
Display
Description
Display
Description
Setting
Application
(T7100F only).
01
00
Conventional
equipment application
(Q7100A).
01
Heat pump application (Q7100C,D)
(fan operation is automatically
selected so go to number 03).
Fan
operation
a,b
.
02
00
Conventional applica-
tions where equipment
controls fan operation
in heat mode.
01
Heat pump and electric heat
applications where thermostat
controls fan operation in heat mode.
Output stages
of heating.
03
Depends
on
subbase
Stage of heat.
01, 02 or
03
01—One stage of heat.
02—Two stages of heat.
03—Three stages of heat.
Heating cycle
04
Depends Stage 1.
03, 04, 03—3 cph used for hot water
rate
a
.
05
a
on model Stage 2.
06, 08,
09
systems or high efficiency
furnaces.
04—4 cph (factory setting for
06
a
Stage 3.
heat pump systems).
—
07
a
09
Emergency heat.
06—6 cph used for conventional
systems.
08—8 cph (factory setting for
conventional systems).
09—9 cph used for electric heat
systems.
Output stages
of cooling
(T7100F only).
08
02
Two stages of cool.
00 or 01 00—No cooling.
01—One stage cooling.
Cooling cycle
rate (T7100F
only).
09
04
Stage 1 at 4 cph.
03
03—3 cph.
10
04
Stage 2 at 4 cph.
Changeover
(T7100F only).
12
00
System setting key is
operational.
01 or 02 01—Heat, Cool, Off (no Auto).
02—Auto only.
Degree
temperature
display.
14
00
Temperature is
displayed in °F.
01
Temperature is displayed in °C.
Displaying
temperature
(T7100F only).
15
00
Temperature is
displayed.
01
Temperature is not displayed.
Extended fan
operation in
heating
(T7100F only)
b
.
19
00
No extended fan
operation after the call
for heat ends.
01
Fan operation is extended
90 seconds after the call for
heat ends.
Extended fan
operation in
cooling
(T7100F only).
20
00
No extended fan
operation after the call
for cool ends.
01
Fan operation is extended
90 seconds after the call for
cool ends.
Fan keys
adjustment
(T7100F only).
21
00
Fan key is operational.
01
Fan key is continuously in the Auto
position.
Remote sensing
(T7100F only).
22
00
Remote sensing not
activated.
01
Remote sensing activated.
Table 6. Thermostat Installer Setup Options.