OPERATION

Figure 6: Operating devices and indicators

(1) Display
(2) Button for day operation 
(3) Button for automatic mode 

Auto

(4) Button for switch-off mode 
(5) Regulator wheel

The T7560H setpoint selector is equipped with 3 operating

modes:

 Automatic 

mode:

The room temperature is regulated according to the control
program of the heating system controller. By means of the
setting wheel, the desired temperature can be adjusted by
±7 °C.

 Daytime 

mode:

The room temperature is maintained continuously or for a
limited period only at the desired daytime temperature.
Adjustments of the desired temperature in automatic mode
are effective.

 Switch-off 

mode:

The heating period is limited or the heating is switched off.
The frost protection remains activated.

Note

The domestic hot water program of the heating system

controller is not affected by the selected operating mode.

For MCR 200, the desired daytime temperature code is

107 and the desired nighttime temperature code is 108.

Adjusting desired temperature

Note

The desired temperature can only be adjusted in auto-

matic mode.

1. If the T7560H is not in automatic mode,

press the 

Auto 

button.

The display reads as follows:

2.  Turn the setting wheel clockwise to increase the desired

temperature. Turn the setting wheel anti-clockwise to lower

the desired temperature.

Note

The adjusted desired temperature is applied in daytime

mode.

Automatic mode

1.   Press the 

Auto

 button.

The display reads as follows:

The T7560H is now set to automatic mode.

Limited daytime mode

1. Press the   button.

The display reads as follows:

2. Turn the setting wheel to adjust the time period. The time

period can be set to intervals of 1–23 hours or 1– 99 days.

For the selected time period, the room temperature is main-

tained at the desired daytime temperature. After the lapse of the

selected period, the T7560H returns to automatic mode.

Continuous daytime mode

1.   Press the   button twice.

The display reads as follows:

The room temperature is maintained at the desired daytime

temperature until a different operating mode is selected.

Limited switch-off mode

1. Press the   button.

The display reads as follows:

2. Turn the setting wheel to select the time period. The time

period can be set to intervals of 1–23 hours or 1– 99 days.

The heating will be switched off for the selected period of time.

After the lapse of the period, the T7560H returns to automatic

mode.

Continuous switch-off mode

1.   Press the   button twice.

The display reads as follows:

The heating remains switched off until a different operating

mode is selected. In the event of danger of frost, the heating

pump and the burner are automatically switched on.

Local operation lock

Activating lock mode:
1.   Simultaneously press the   and the 

Auto

 buttons for at

least 2 seconds.

The display reads as follows:

As soon as you release the buttons, the display shows the

previously selected operating mode.

The T7560H is now locked and protected against accidental

operation. As soon as the operating mode button or the setting

wheel are activated, the message 

 is displayed.

Deactivating local operation lock:
1.   Simultaneously press the   and the 

Auto 

button for at least

2 seconds.

The display reads as follows:

As soon as you release the buttons, the display shows the

previously selected operating mode.

The lock is now deactivated.

Note

The local operation lock can be activated/deactivated in

any operating mode.

TECHNICAL DATA

Sensor element:

NTC thermistor

Resistance:

20 kOhm at 25 °C

Temperature range:

–15...+40 °C

Dimensions (H

×

W

×

D): 103 

×

 98 

×

 28 mm

Installation:

Installation on wall

Max. ambient
temperature / humidity: 0...50 °C / 5...95 %
Max. storage temperature /
humidity:

–35...+70 °C / 5...95 %

Electric connection:

Terminals for max. 1.0 mm

2

wire diameter

Protection class:

IP 30, DIN 40 050

or IEC 144

Timer programs:

×

 daytime mode, limited period

×

 switch-off mode, limited period

Time range:

1 hour (h) to 99 days (d)

Time intervals:

1...23 hours (h) at intervals of 1 hour

1...99 days (d) at intervals of 1 day

For technical information on NTC thermistor:
see publication GE 3R-1106.

Centra Regelungstechnik

Honeywell AG
Böblinger Strasse 17
D-71101 Schönaich
Telephone:

++49 (0)7031 637 01

Fax:

++49 (0)7031 637 574

http://www.honeywell.de/hga

Subject to change

Company 

 

certified

This document replaces all previously issued instructions and is

only applicable to the product with which it is supplied.
.

No. 7157407

EN1H-155 GE51R0100