T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
41
63-7147—05
T775L Replacement for W7100C
Discharge Air Controller
This replacement example illustrates how a T775L using a
T775S Expansion module is configured to replace a two-stage
Heat and four-stage Cool W7100C Discharge Air Controller.
Fig. 48 illustrates the wiring connections for the W7100C
Discharge Air Controller.
Fig. 49 and Table 5 on page 43 illustrate the wiring and
configuration of the T775L controller.
Fig. 48. W7100C wiring connections (pre-existing control).
NOTE: The T775L Replacement for W7100C Discharge Air Controller continues on the next page.
M28017
1
R1
B1
W1
TR
TR
L1 (HOT)
L2
1
W
R
3
1
2
Q209A
MINIMUM POSITION
POTENTIOMETER
H205 OUTDOOR
AIR CHANGEOVER
C7100
DISCHARGE
SENSOR
C
B
A
C
B
A
C
B
A
C
B
A
C
B
A
GND
Y
B
W
TR
T
1
5
2
4
3
T1
R
TR
6
10
7
9
8
P
P1
24VAC
ECONO
CHANGE
OVER
RESET
STAGES
SATELLITE
REMOTE
SETPOINT
SENSOR
RESET °F
CONTROL BAND
HEAT 1
HEAT 2
COOL 4
COOL 3
COOL 2
C
B
A
COOL 1
SETPOINT °F
COOL 3
COOL 1
HEAT 2
HEAT 1
COOL 4
COOL 2
1K1
W
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
USE ONLY WITH SPACE RESET SENSOR. CONNECT IN SERIES AS SHOWN.
WHEN RESET NOT USED, JUMPER TERMINALS 6 AND 7.
SET HEAT AND COOL DISCHARGE SETPOINTS USING REMOTE SETPOINT POTENTIOMETERS. TURN SETPOINT KNOB ON W7100
TO MINIMUM POSITION. USE OF THE S963B1086 WILL CHANGE SETPOINT RANGE TO 40 TO 140°F.
GROUND CASE OF REMOTE SETPOINT POTENTIOMETER TO PREVENT PROBLEMS DUE TO STATIC ELECTRICITY.
WHEN CHANGEOVER TERMINALS 9 AND 10 ARE USED ON HEAT/COOL MODELS, JUMPER TERMINALS 9 AND 10 TO CHANGE OVER TO
HEATING (LOCKS OUT COOLING WHEN JUMPERED).
WHEN ECONOMIZER IS NOT USED, JUMPER TERMINALS Y AND 9 WITH THE 510 OHM, 1/4 WATT, 5 PERCENT RESISTOR CONTAINED
IN THE 4074EFV BAG ASSEMBLY.
REMOVE FACTORY INSTALLED 400 OHM RESISTOR JUMPER AND RECONNECT FOR COOLING-ONLY MODE, 4-STAGE OPERATION
(CHANGE VALUE FOR OTHER NUMBER OF STAGES). FOR 2-STAGES IN HEATING MODE, USE 200 OHM, 1/8 WATT RESISTOR FOR
BEST OPERATION.
3
2
4
5
7
6
8
4
4
S963B1078 OR S963B1086
COOLING REMOTE
SETPOINT POTENTIOMETER
S963B1078 OR S963B1086
HEATING REMOTE
SETPOINT POTENTIOMETER
2K2
2
3
T7047C1025 SPACE RESET SENSOR OR
C7031G1016 OUTDOOR RESET SENSOR
S963B1037 REMOTE
POTENTIOMETER
W
R
W
R
W
200 OHM (2 HEATING STAGES)
1K1
2K1
2K1 400 OHM (4 COOLING STAGES)
W
B
R
(MAKE ON TEMP. DROP)
R822N RELAY (1K)
R822N RELAY (2K)
T675A HEAT/COOL SWITCH
CHANGEOVER
POWER
SUPPLY
2K2
°F
L1 (HOT)
L2
B
W
R
M955 MOTOR
(ECONOMIZER)
8
7
7
6
5
5
W7100C DISCHARGE AIR CONTROLLER
COOL
HEAT