background image

T775 SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS

63-7147—3

4

1

 See form 62-0265 - 

Temperature Sensor for the T775 Series 

2000 Stand-alone Controller

Accessories

• 107324A – Bulb Holder, duct insertion
• 107408 – Heat Conductive Compound, 4 ounce
• 50001774-001 – Immersion Well, stainless steel 304, 

1/2 in. threading

FEATURES

In Table 1, a check mark (

!

) indicates that the controller 

model has this feature. A number indicates the quantity (e.g., 
the T775M2030 has 4 standard SPDT relay outputs), and 
“n/a” indicates the feature is not applicable to that controller 

model.

Table 1. T775 Controller Features by Model Number.

Feature

T77

5

A2009

T77

5

B2016

T77

5

B2024

T77

5

B2032

T77

5

B2040

T77

5

L2007

T7
75M

2006

T7
75M

2014

T7
75M

2022

T7
75M

2030

T7
75M

2048

T77

5

P2003

T77

5

R2001

T77

5

R2019

T77

5

R2027

T77

5

R2035

T77

5

R2043

T77

5

U2006

T77

5

S2008

User Interface

2x4 inch LCD display with English language display

!

!

! !

!

!

!

!

!

!

!

! !

!

!

!

!

!

n/a

Keypad lockout

!

!

!

! !

!

!

!

!

!

!

! !

!

!

!

!

!

n/a

Applications

Standard heating/cooling

!

!

!

! !

!

!

!

!

!

!

! !

!

!

!

!

!

!

Modulating

!

!

!

!

!

!

!

!

!

Boiler/Chiller

!

!

!

! !

!

!

!

!

!

!

! !

!

!

!

!

!

!

Reset

!

! !

!

!

!

!

!

!

Stage (Loop) control of up to 12 relays

!

!

!

Temperature, humidity, pressure, or other 

application requiring 0-10 Vdc or 4-20 mA input

!

Expansion module (4-relays per module; 2 modules 

max.)

!

Power

24 or 120/240 Vac with separate earth ground

!

!

!

! !

!

!

!

!

!

!

! !

!

!

!

!

!

!

Relay Outputs

SPDT

!

!

!

! !

!

!

!

!

!

!

! !

!

!

!

!

!

!

Number of standard

1

2

4

2

4

4

0

4

2

4

2

4

4

4

2

2

0

2

4

Number of floating

(each floating output eliminates 2 relays)

0

1

2

1

2

0

0

0

0

0

0

0

2

0

0

1

0

0

0

Runtime displayed on relays 1-4 (optional)

!

!

!

! !

!

!

!

!

!

!

! !

!

!

!

!

!

n/a

Configurable minimum off time

!

!

!

! !

!

!

!

!

!

!

! !

!

!

!

!

!

!

Expandable to 12 relays using T775S expansion 

modules (4 relays per expansion module)

!

!

!

Warm weather shutdown

!

n/a

Modulating Outputs

Number of outputs

0

0

0

0

0

0

2

2

2

2

2

0

0

2

2

0

2

2

0

Independently selectable for 0-10 Vdc, 2-10 Vdc, 

4-20 mA, or Series 90

!

!

!

!

!

!

!

!

!

Modulating high/low limit control

!

!

!

!

!

n/a

Digital Output

Number of outputs

0

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

0

0

0

High, low, and differential alarm

!

Summary of Contents for T775 Series

Page 1: ...APPLICATION GUIDE AND CROSS REFERENCE 63 7147 3 T775 Series 2000 Electronic Stand Alone Controllers ...

Page 2: ...75B 8 Chiller T775B 9 Chiller Rotary Compressor T775B 10 Cooling Tower Control T775B2040 11 Time based Control of Fan Pump etc T775 all models 12 Damper or Valve Modulation T775M or T775R 13 Hot Water Reset T775R 14 Chilled Water Reset T775R 16 Multi Stage Boiler Control No Reset T775P 18 Multi Stage Boiler Control Reset T775P 19 Multi Stage Chiller Control No Reset T775P 21 4 Stage with Pump Outp...

Page 3: ...A Refer to the T775 Series 2000 Electronic Stand Alone Controllers Specification Data form 63 1318 01 COMPATIBLE COMPONENTS Temperature Sensors1 The controller accepts 1 097 Ohms PTC at 77 F 25 C 50021579 001 Standard sensor included with all models except T775U2006 and NEMA 4X models T775 SENS STRAP Strap on sensor with wiring box T775 SENS WR Water resistant with 5 foot leads included with NEMA ...

Page 4: ...4 inch LCD display with English language display n a Keypad lockout n a Applications Standard heating cooling Modulating Boiler Chiller Reset Stage Loop control of up to 12 relays Temperature humidity pressure or other application requiring 0 10 Vdc or 4 20 mA input Expansion module 4 relays per module 2 modules max Power 24 or 120 240 Vac with separate earth ground Relay Outputs SPDT Number of st...

Page 5: ...1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Setpoints Maximum number of setpoints 1 2 4 2 4 4 2 6 4 6 4 1 4 6 4 2 2 4 n a Range 40 to 248 F 40 to 120 C Maximum high setpoint option irreversible n a Integral and Derivative Options Integral time selectable from 0 to 3 600 seconds n a Derivative time selectable from 0 to 3 600 seconds n a Staging Standard staging First on first off Equalized runtime On delay and...

Page 6: ...ct For all T775 Series 2000 controllers the derivative default value is factory set to zero no derivative control It is strongly recommended that the derivative remain at zero 0 unless you have a very good reason to adjust it Derivative control is not needed in the vast majority of HVAC applications Differential vs Throttling Range Differential is used for relay outputs and throttling range is use...

Page 7: ...single reset curve is programmed for the first output and is used by all outputs setup for Reset 2 For subsequent outputs a setpoint offset is used if that output is also being Reset When Reset is programmed the home screen conveniently displays the calculated Heat Cool setpoint s for the outputs based on the reset curve Setback Optional Description The Setback temperature option is available only...

Page 8: ...ature rises to 96 F 36 C Relay 4 powers the high temperature alarm NOTE If no alarms are present Relay 2 and 4 may be used as additional heating and cooling relays Programming Example Relay 1 Enables boiler circuit Program for Heat Setpoint 65 F 18 C Differential 10 F 12 C Relay 2 Low temperature alarm circuit Program for Heat Setpoint 55 F 13 C Differential 1 F 17 C Relay 3 Enables cooling circui...

Page 9: ...ferential the sump water freeze up protection is provided by energizing Heating relay 4 Programming Example Relay 1 Controlling spray water pump and or valve Program for Cool Setpoint 60 F 16 C Differential 5 F 12 C Relay 2 Controlling fan 1 Program for Cool Setpoint 65 F 18 C Differential 5 F 12 C Relay 3 Controlling fan 2 Program for Cool Setpoint 70 F 21 C Differential 5 F 12 C Relay 4 Controll...

Page 10: ...F 17 C Relay 2 Compressor 1 controlling the Open solenoid valve Program for Cool Setpoint 56 F 13 C Differential 2 F 17 C Relay 3 Compressor 2 controlling the Close solenoid valve Program for Cool Setpoint 56 F 13 C Differential 2 F 17 C Relay 4 Compressor 2 controlling the Open solenoid valve Program for Cool Setpoint 60 F 16 C Differential 2 F 17 C IMPORTANT After the desired value is selected b...

Page 11: ... C Cool Sensor B IMPORTANT After the desired value is selected be sure to press the or or HOME button in order to save that value in the controller s memory IMPORTANT By programming the relay 3 setpoint at 55 F 13 C the T775 is wired to cutoff power to the cooling fan Once the outside air temperature rises above 55 F 13 C relays 1 and 2 control the fan speed based on their setpoints for Sensor A S...

Page 12: ...ntrol the device fan pump etc Program for Setpoint 0 F 17 C Differential 1 F 17 C Sensor Sensor B Setback 100 F 38 C Action Cool Now the relay will close at 6 00 a m and open at 6 00 p m daily 1 The Date must be set before the Time is set NOTE Keep in mind that if the scheduler is energized all relays will follow the time schedule If you do not want some outputs to go into a setback mode choose Sc...

Page 13: ...hrottling Range 10 F 12 C Sensor Sensor A Heat or Cool IMPORTANT After the desired value is selected be sure to press the or or HOME button in order to save that value in the controller s memory Wiring See Figures 8 9 for wiring connections for the T775M with examples of an MS75xx actuator and an ML7425 valve actuator Fig 8 T775M Wiring Damper Modulation 2 10 Vdc shown Fig 9 T775M Wiring Valve Mod...

Page 14: ... button in order to save that value in the controller s memory IMPORTANT By programming the boiler setpoint at 210 F 99 C the T775 has established 210 F 99 C as the highest operating point that will be allowed when the outside temperature falls below 20 F 7 C As the outside temperature increases above 20 F 7 C the boiler will be reset downward per the reset ratio until it reaches the minimum setpo...

Page 15: ...nsor B NOTE The alternate Home screens do not show live updates of the sensor temperature They show the temperature only at the moment the button is pressed 1 From the Home screen use the button to verify the setpoint temperature for each output 2 Then press the HOME button to view the actual outside air temperature sensor B Fig 14 Boiler Discharge Temperature Setpoint vs Outside Temperature L1 HO...

Page 16: ...eset YES OTHER Relay 1 Control to the chilled water temperature Program for Refer to the reset curve in Fig 15 Setpoint Max A1 Chiller 60 F 16 C Reset B1 Outside Min 70 F 21 C Setpoint Min A2 Chiller 45 F 7 C Reset B2 Outside Max 90 F 32 C Differential 10 F 12 C Cool IMPORTANT After the desired value is selected be sure to press the or or HOME button in order to save that value in the controller s...

Page 17: ...the effective setpoint is adjusting correctly based on the outside air temperature sensor B NOTE The alternate Home screens do not show live updates of the sensor temperature They show the temperature only at the moment the button is pressed 1 From the Home screen use the button to verify the setpoint temperature for each output 2 Then press the HOME button to view the actual outside air temperatu...

Page 18: ...e first stage energizes A negative time causes the pump to energize after the first stage energizes 2 The Postpurge time causes the pump to run for the set number of seconds after the last stage de energizes Return to the Setup menu and select Alarms High Alarm YES High Limit 220 F 93 C NOTE This model has Equal Runtime options which can be configured with the Lead Lag output option in Setup Stage...

Page 19: ... YES or NO Temperature 30 to 100 F 1 to 38 C STG4 Pump Relay 4 controls the pump output 1 Enable YES Exercise YES or NO Prepurge 300 to 300 seconds default is 0 Postpurge 0 to 300 seconds default is 0 Return to the Setup menu and select Alarms High Alarm YES High Limit 220 F 104 C Stages 1 3 Control to the discharge water temperature Program for Refer to the reset curve in Fig 21 Boiler Max 210 F ...

Page 20: ...in Setup Press and hold the MENU button for 5 seconds to enter Setup mode Select the Outputs menu and then select Stages 3 T775 assigns pump to Relay 4 Options On Delay and Off Delay Seconds 0 to 3 600 default is 0 STG4 Pump Relay 4 controls the pump output 1 Enable YES Exercise YES or NO Prepurge 300 to 300 seconds default is 0 Postpurge 0 to 300 seconds default is 0 Return to the Setup menu and ...

Page 21: ... A is sensing discharge water and controls 4 stages Sensor B is sensing outside temperature and is used for reset Sensor C is sensing the return water temperature NOTE Control can be to either sensor A or C Operation As the heating load increases additional stages of heat will cycle ON as the boiler water temperature decreases In this example the T775P provides four stage control when the effectiv...

Page 22: ... boiler setpoint at 210 F 99 C the T775 has established 210 F 99 C as the highest operating point that will be allowed when the temperature falls below 20 F 7 C As temperature increases above 20 F 7 C the boiler will be reset downward per the reset ratio until it reaches the minimum setpoint of 160 F 99 C at 70 F 21 C and above outdoor temperature Fig 25 Staging Behavior when the effective setpoin...

Page 23: ...re They show the temperature only at the moment the button is pressed 1 From the Home screen use the button to verify the setpoint temperature for each output 2 Then press the HOME button to view the actual outside air temperature sensor B Fig 28 Boiler Discharge Temperature vs Outside Temperature M24556 T775 BUS TERMINALS PROVIDE WIRING CONNECTIONS TO FROM T775P L AND T775S POWER WITH 24 VAC OR 1...

Page 24: ...NU button for 5 seconds to enter Setup mode Select the Outputs menu and then select Relays 3 Loops 1 Options DI Options Disable acts as low pressure cutoff Loop 1 Relays 3 Loop 1 Reset NO Loop 1 Chiller cooling Program for Setpoint 62 F 17 C Throttling Range 12 F 11 C Sensor A Cool Relay 4 Low temperature cutoff for freeze protection Program for Setpoint 40 F 4 C Differential 4 F 16 C Sensor B Hea...

Page 25: ...Programming Example Program in Setup Press and hold the MENU button for 5 seconds to enter Setup mode Select the Outputs menu and then select Relays 10 4 heat and 6 cool Loops 2 Loop 1 Relays 4 Loop 1 Reset NO1 Loop 2 Relays 6 Loop 2 Reset NO NOTES 1 The Integral setup parameter can be left at the factory default setting or adjusted as needed for each loop 2 The On Delay and Off Delay setup parame...

Page 26: ...5S C NO NC C NO NC C NC NO C NC NO T T COOL 5 COOL 6 COM NO COM NO 1 3 2 T775 BUS TERMINALS PROVIDE WIRING CONNECTIONS TO FROM T775L AND T775S USE PIGTAIL CONNECTIONS TO WIRE THE T775 BUS TERMINALS ON THE FIRST T775S SECOND T775S MUST HAVE A JUMPER INSTALLED AS SHOWN AT THE JUMPER TERMINAL POWER WITH 24 VAC OR 120 240 VAC AT THE APPROPRIATE TERMINAL BLOCK 24 VAC POWER TERMINAL BLOCK 1 2 3 M27239 C...

Page 27: ...ep in mind these values are valid for proportional control and will differ in a PID loop where integral usually desired and derivative less often required are set to non zero values Integral and derivative time may need to be adjusted along with the throttling range Programming Example Program in Setup Press and hold the MENU button for 5 seconds to enter Setup mode and then select Sensors Sensor ...

Page 28: ...utton for 5 seconds to enter Setup mode and then select Sensors Sensor A Type 0 10V Units Minimum Value 0 0 Maximum Value 100 0 NOTE Sensor A is a 0 10 Vdc CO2 sensor C7232 with a range of 0 to 2 000 PPM IMPORTANT After the desired value is selected be sure to press the or or HOME button in order to save that value in the controller s memory The T775U displays the sensor output as a percentage Use...

Page 29: ... W973A Logic Panel continues on the next page W973A T Y B W R T T 1 5 2 4 3 T1 R T7067 THERMOSTAT 1 5 2 4 3 8 7 6 SENSOR STAT 24V ECONO MOD HEAT MOD COOL WC BC RC RH BH WH W R L1 HOT L2 L1 HOT L2 R 1 HEAT 2 1 COOL 2 C 20 N H COOL 1 COOL 2 HEAT 2 HEAT 1 T675A HIGH LIMIT T675A COMPRESSOR LOCKOUT 1 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED W973A SHOWN W973B HAS 3 HEA...

Page 30: ...TERMINALS W AND R MINIMUM DRIVE CLOSED SIGNAL LESS THAN 0 17 VDC MAXIMUM DRIVE OPEN SIGNAL IS GREATER THAN 1 7 VDC USE SEPARATE TRANSFORMER FOR T775M WHEN USING 24 VAC A 250 OHM RESISTOR PROVIDES 40 AUTHORITY WHEN USING A 150 OHM MINIMUM POSITION POTENTIOMETER INSERT 340 OHM RESISTOR INCLUDED ACROSS TERMINALS R AND W POWER WITH 24 VAC OR 120 240 VAC AT THE APPROPRIATE TERMINAL BLOCK 24 VAC POWER T...

Page 31: ... Discharge Sensor C7046 Sensor B Discharge C7046D1008 Heating Cooling Motor M954 Series 90 4 20 mA 0 10 Vdc or 2 12 Vdc motor may be used Fan Start Fan Start Relay If a relay is available it can be used for fan control e g 1 stage Heat and 2 stage Cool using the T775M2030 Economizer M955 With the T775M2030 there are two modulating outputs Therefore two of the three functions Heat Cool or Economize...

Page 32: ... 37 and Table 4 on page 34 illustrate the wiring and configuration of the T775R controller Fig 36 W964F Wiring Connections Pre existing Control NOTE The T775R Replacement for W964F Aquatrol Panel with Floating Actuator continues on the next page L 5 4A 4 1 2 3 A B C D N T3 T3 T2 T2 7 6 T7044A T7043A T7043B T 1 2 3 Y B R W G M944B 1 3 W964F L N 1 120 V 60 HZ POWER SUPPLY PROVIDE DISCONNECT MEANS AN...

Page 33: ...R W C S V T T C SENSOR A STANDARD TEMPERATURE SENSOR C NO NC C NO NC C NC NO C NC NO RELAY 3 RELAY 2 RELAY 1 RELAY 4 120 COM 240 T T SENSOR B OUTDOOR SENSOR T775R 6 120 VAC 7 7 OTHER MOTORS SUCH AS 4 20 MA 0 10 VDC AND 2 10 VDC MAY BE USED ON THE MOD 1 OUTPUT TO VERIFY OUTPUT TEST OPEN CIRCUIT VOLTAGE BETWEEN THE MOD 1 TERMINALS W AND R MINIMUM DRIVE CLOSED SIGNAL LESS THAN 0 17 VDC MAXIMUM DRIVE ...

Page 34: ...re sensor See Temperature Sensors on page 3 Reset ratio and parallel shift n a Reset programming in the T775R provides the reset curve On Off motor control Jumper terminals 1 and 2 on the W964F If the W964F provided On Off motor control then wire motor to a relay output on the T775R to provide On Off control Actuator motor speed n a Use the Integral Time and Throttling Range to tune the T775R cont...

Page 35: ...ES SHOWN WITH DEVICE ENERGIZED REFER TO SPECIFICATIONS FOR NUMBER OF SWITCHES AUXILIARY POTENTIOMETER ON S984J ONLY TERMINAL LABELED AUX THIS HOOKUP IS FOR A COOLING SYSTEM FOR A HEATING SYSTEM REVERSE W AND B WHEN SHIPPED LEADS ARE JOINED WITH A WIRE NUT TO DELAY STAGES ON REMOVE WIRE NUT FROM ORANGE AND WHITE LEADS AND CONNECT TO DELAY TIMER TO DELAY STAGES OFF REMOVE WIRE NUT FROM BLUE AND WHIT...

Page 36: ...ntrol based on outside temperature Sensor A must be the inside sensor and Sensor B must be the outside sensor Delay Timer S400A Use the On Delay and Off Delay programmable parameters of the T775L Throttling Range n a Set the programmable Throttling Range parameter to match the application Reset T991B or W902A if used Reset programming in the T775L provides the reset curve Loads 1 5 n a Program the...

Page 37: ... AS SHOWN WHEN RESET NOT USED JUMPER TERMINALS 6 AND 7 SET HEAT AND COOL DISCHARGE SETPOINTS USING REMOTE SETPOINT POTENTIOMETERS TURN SETPOINT KNOB ON W7100 TO MINIMUM POSITION USE OF THE S963B1086 WILL CHANGE SETPOINT RANGE TO 40 TO 140 F GROUND CASE OF REMOTE SETPOINT POTENTIOMETER TO PREVENT PROBLEMS DUE TO STATIC ELECTRICITY WHEN CHANGEOVER TERMINALS 9 AND 10 ARE USED ON HEAT COOL MODELS JUMP...

Page 38: ...next page M28018 T775 BUS TERMINALS PROVIDE WIRING CONNECTIONS TO FROM T775L AND T775S SETUP THE CONTROL T6031 OR T765 SO THAT IT CLOSES ON A TEMPERATURE FALL POWER WITH 24 VAC OR 120 240 VAC AT THE APPROPRIATE TERMINAL BLOCK 24 VAC POWER TERMINAL BLOCK 1 2 T775L T775S C NO NC C NO NC C NC NO C NC NO T T L1 HOT L2 24 VAC COM NO COM NO COM NO COM NO HEAT 2 HEAT 1 C NO NC C NO NC C NC NO C NC NO 3 1...

Page 39: ...mizer module e g W7212 to provide economization Heat Cool switch changeover T675A Connect the Digital Input terminal to an outdoor temperature control e g T6031 or T675A Program the Digital Input for Setback using 40 F 40 C for the T675A cooling setpoint to lock out the cooling system during cold weather Setpoint and Reset Setpoint and Reset dial Reset programming in the T775L provides the reset c...

Page 40: ...on T775A2009 Johnson model 1 SPDT temperature A350A B with 1 S350 Johnson T775B2032 Johnson model Multiple SPDT temperature A350A B with up to 3 S350s Johnson T775B2040 Johnson model Multiple SPDT temperature A350A B with more than 3 S350s Johnson T775B2040 plus additional T775Bs as needed Johnson model Multiple SPDT temperature A350P Johnson T775M2006 Johnson model 1 mod temperature A350P with up...

Page 41: ...5A1063 Honeywell 5 to 95 RH 4 SPDT T775U2006 5001774 001 T775U has only 2 relays H775B1005 Honeywell 5 to 95 RH 2 SPDT T775U2006 5001774 001 H775C1004 Honeywell 5 to 95 RH 4 SPDT T775U2006 5001774 001 T775U has only 2 relays H775D1003 Honeywell 5 to 95 RH 2 SPDT T775U2006 5001774 001 H775E1002 Honeywell 5 to 95 RH 2 SPDT T775U2006 5001774 001 T4031A1008 Honeywell 30 to 50 SPST 5 ft T775A2009 50017...

Page 42: ...se stainless well T6031D1007 Honeywell 40 to 180 SPDT 7 5 ft armored T775A2009 5001774 001 Protect sensor wires T6031D1015 Honeywell 40 to 180 SPDT 5 5 ft T775A2009 5001774 001 T6031D1031 Honeywell 0 to 70 SPDT 5 5 ft T775A2009 5001774 001 T6031D1049 Honeywell 30 to 270 SPDT 5 5 ft T775A2009 5001774 001 T6031E1004 Honeywell 40 to 180 SPDT 5 5 ft T775A2009 5001774 001 T6031F1010 Honeywell 55 to 90 ...

Page 43: ...01 Add S445A1010 to convert T775 to manual reset T675B1028 Honeywell 20 to 50 SPDT 10 ft T775A2009 5001774 001 Add S445A1010 to convert T775 to manual reset T675B1032 Honeywell 80 to 220 SPDT 10 ft T775A2009 50021579 001 x3 or C7031J2009 or C7100D1001 Averaging T678A1015 Honeywell 0 to 100 2 SPDT 20 ft T775B2032 5001774 001 T678A1080 Honeywell 160 to 260 2 SPDT 5 ft T775B2032 5001774 001 T678A1163...

Page 44: ...DT T775M2014 T775G1013 Honeywell 20 to 220 3 SPDT T775M2014 T775G1021 Honeywell 20 to 220 3 SPDT T775M2014 T775G1039 Honeywell 20 to 220 4 SPDT T775M2014 T775J1001 Honeywell 20 to 240 1 SPDT T775R2035 T775J1019 Honeywell 20 to 240 None T775R2043 T775J1027 Honeywell 20 to 240 None T775R2043 T775J1035 Honeywell 20 to 240 None T775R2043 T775J1043 Honeywell 20 to 240 1 SPDT T775R2027 T775J1050 Honeywe...

Page 45: ...6 ft L480G1044 20 to 60 F None T775A2009 5001774 001 Add S445A1010 to convert T775 to manual reset A19ACA 15 Johnson 30 to 100 SPST 10 ft L480G1044 None T775A2009 5001774 001 Add S445A1010 to convert T775 to manual reset A19ADB 1 Johnson 100 to 240 SPST 6 ft L4008E1156 110 to 290 F 121371L 3 in insulation T775A2009 5001774 001 Add S445A1010 to convert T775 to manual reset A19AAB 4 Johnson 30 to 11...

Page 46: ...0 to 100 F or T678A1445 55 to 175 F 1 2 112622AA T775B2024 5001774 001 T678 has no weatherproof enclosure 3 4 112630AA A28MA 2 Johnson 40 to 120 2 SPDT 6 ft T678A1437 0 to 100 F or T678A1445 55 to 175 F 1 2 112622AA T775B2024 5001774 001 T678 has no weatherproof enclosure 3 4 112630AA A36AHA 50 Johnson 55 to 95 4 SPDT 18 in None 112620BB T775B2040 5001774 001 A36AHA 52 Johnson 55 to 95 4 SPDT 6 ft...

Page 47: ...2 123869A T775A2009 5001774 001 3 4 123870A 1609 104 White Rodgers 30 to 90 SPST 20 ft T6031A1060 1 2 123869A T775A2009 5001774 001 3 4 123870A 1609 105 White Rodgers 30 to 90 SPST 5 ft T4031A1073 1 2 123869A T775A2009 5001774 001 3 4 123870A 1609 106 White Rodgers 30 to 90 SPST 5 ft T675A1706 0 to 100 F F None T775A2009 5001774 001 Fast response element 1609 114 White Rodgers 20 to 90 SPST 8 ft T...

Page 48: ...0 to 90 F 1 2 123869A T775A2009 5001774 001 3 4 123870A TC4112 Barber Colman 100 to 260 SPDT 6 ft L6008A1192 100 to 240 F 121371A T775A2009 TC4115 Barber Colman 40 to 120 SPDT 6 T6031A1136 30 to 90 F 1 2 123869A T775A2009 3 4 123870A TC4151 Barber Colman 70 to 120 SPDT 30 ft T475A1057 1 2 121371P T775R2035 5001774 001 The T775R is a Reset controller 3 4 121371Q TC4152 Barber Colman 70 to 120 SPDT ...

Page 49: ... to convert T775 to manual reset Ranco ETC 111000 Ranco T775A2009 ETC 111100 Ranco T775M2048 ETC 112000 Ranco T775M2048 ETC 112100 Ranco T775M2048 ETC 141000 Ranco T775B2016 ETC 211000 Ranco T775B2932 ETC 211100 Ranco T775M2048 ETC 212000 Ranco T775B2032 ETC 212100 Ranco T775M2048 ETC 24100 Ranco T775B2016 Table 7 Cross Reference Continued Old Control Manufacturer Temperature F Humidity Range RH S...

Page 50: ...on Floating Output Integral Voltage Options Type based Type based Type based Type based Type based Irreversible High Set Point Limit Lo Hi or Hi Lo staging Modulating Outputs T775M2048 T775R2027 T775R2027 Nema 4x Models T775B2016 Optional Input Sensor Outdoor Reset Power Supply Voltage 20 to 28 Vac 24 120 240 Vac 20 to 28 Vac 24 120 240 Vac 24Vac 24 120 240 Vac 24 120 240 Vac 120 Vac 24 120 240 Va...

Page 51: ...T775 SERIES 2000 ELECTRONIC STAND ALONE CONTROLLERS 51 63 7147 3 NOTES ...

Page 52: ...trol Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2008 Honeywell International Inc 63 7147 3 J I Rev 02 08 ...

Reviews: