T775R SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0249—13
30
Fig. 75. Setup - Outputs - Floating Relay - Derivative.
3.3.6.1.1.3. DERIVATIV
(modulating/floating
relay only)
The Derivative option displays only on the T775R2001
and the T775R2035 models when the Type option =
Floating.
1.
From the menu, use the
and
buttons to high-
light DERIVATIV.
2.
Press the
button to display the actuator value.
3.
Use the
and
buttons to increase/decrease the
desired number of seconds.
Default: 0 seconds
Range: 0 to 3,600 seconds)
4.
Press the
button to accept the value and display
the SCHEDULE option.
Continue with “3.3.6.2. SCHEDULE” for the remaining
relay selections.
Fig. 76. Setup - Outputs - Relay - Schedule.
3.3.6.2. SCHEDULE
This selection displays only if “Use Sched = YES” is
selected during the Output Options setup (Refer to “3.3.5.
OPTIONS” on page 26). When selected, individual
outputs default to follow the schedule.
1.
Press the
button to display the Schedule values.
2.
Use the
and
buttons to select YES or NO.
Default: YES
3.
Press the
button to accept the value and return to
the Relay menu.
An individual output can be selected to be controlled or
not controlled by the schedule.
If NO is selected, the Setback selection does not appear
in the Program menu for this output.
Fig. 77. Setup - Outputs - Relay - Reset.
3.3.6.3. RESET
The Reset menu displayed (Fig. 77) depends on whether
the controller has modulating outputs:
• For controllers with modulating outputs, the first output
(MOD 1) is settable for Reset, which then enables
Reset to be set for the Relay outputs. Refer to
“3.3.3.1.6. RESET” on page 25.
• For controllers with no modulating outputs, this
selection enables the controller’s Reset function, and
allows each relay output to be individually programmed
for Reset or No Reset.
IMPORTANT
To use the Reset function of the controller, the
first output (MOD 1 or Relay 1 depending on the
model) must be set for Reset.
1.
Press the
button to display the Reset values.
2.
Use the
and
buttons to select YES or NO.
Default: NO
3.
Press the
button to accept the value and return to
the Relay menu.
• If you select YES, then
all
other outputs display this
Setup option and will use the reset curve programmed
for the first output.
• If you select NO, then No Reset is configured for that
output and all other subsequent outputs.
SETUP
OUTPUTS
FLOAT 1
DERIVATIV
ENTER
DERIVATIVE
TIME FOR
FLOAT 1
SETUP
OUTPUTS
FLOAT 1
DERIVATIV
0
SEC
M24354
SETUP
OUTPUTS
RELAY 1
SCHEDULE
SETUP
OUTPUTS
RELAY 1
SCHEDULE
USE
SCHEDULE
FOR
OUTPUTS
YES
NO
M24355
SETUP
OUTPUTS
RELAY 1
RESET
USE
RESET
FOR
RELAY 1
YES
NO
SETUP
OUTPUTS
RELAY 1
RESET
USE
RESET
FOR
RELAY 1
YES-BOILER
YES-OTHER
NO
CONTROLLERS WITH MODULATING OUTPUTS
CONTROLLERS WITH NO MODULATING OUTPUTS
SETUP
OUTPUTS
RELAY 1
RESET
SETUP
OUTPUTS
RELAY 1
RESET
M24356