T775U SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLER
62-0255—09
28
Default: 60°F (16°C)
Range: -40°F to 248°F (-40°C to 120°C)
3.
Press the
u
button to accept the value and display
the menu.
Fig. 62. Program - Sensor.
2.1.3. SENSOR
This sub-menu choice is only available on the T775U2016
model.
1.
From the menu, use the
p
and
q
buttons to highlight
SENSOR A or SENSOR B.
2.
Press the
u
button to accept the sensor selection
and display the next option.
Fig. 63. Program - Throttling Range or Differential.
2.1.5. THROTTLING RANGE or
DIFFERENTIAL
Throttling Range displays for Modulating outputs.
Differential is used for the Relay outputs.
1.
From the menu, use the
p
and
q
buttons to highlight
THROT RNG or DIFFERNTL.
2.
Press the
u
button to display the throttling range
value.
3.
Use the
p
and
q
buttons to increase/decrease the
desired value.
Default: 20°F (-6.6°C)
Range: 1°F to 150°F (1°C to 66°C)
4.
Press the
u
button to accept the value and display
the next option.
The Throttling Range brackets the setpoint setting, e.g., if
the setpoint is 72°F and the throttling range is 10°F, then
the effective throttling temperature range is 67°F to 77°F.
In heating mode, the Differential is below the setpoint. The
relay de-energizes when the temperature rises to the
setpoint. As the temperature drops to the setpoint minus
the Differential, the relay energizes.
In cooling mode, the Differential is above the setpoint. The
relay de-energizes when the temperature falls to the
setpoint. As the temperature rises to the setpoint plus the
Differential, the relay energizes.
Fig. 64. Program - Action.
2.1.6. ACTION
1.
From the menu, use the
p
and
q
buttons to highlight
ACTION.
Default: HEAT
2.
Press the
u
button to display the action selections.
3.
Use the
p
and
q
buttons to select the desired value.
4.
Press the
u
button to accept the highlighted selec-
tion and display the next option.
PROGRAM
MOD
1
SENSOR
MENU
PROGRAM
MOD 1
SENSOR
SELECT
SENSOR
FOR
MOD 1
SENSOR A
SENSOR B
M28660
ENTER
THROTLLING
RANGE FOR
MOD 1
PROGRAM
MOD1
THROT RNG
MENU
PROGRAM
MOD 1
THROT RNG
20
F
o
M24582
PROGRAM
MOD
1
ACTION
MENU
PROGRAM
MOD 1
ACTION
SELECT
ACTION
FOR
MOD 1
HEAT
COOL
REV ACT
DIR ACT
HUMID
DEHUMID
M24583