This equipment shall be installed in accordance with the requirements of the National Electrical
Code (NEC), ANSI/NFPA 70, or the Canadian Electrical Code (CEC), C22.1. It is supplied as
“open equipment” that is intended to be mounted on a sub-panel within an enclosure. The
suitability of the enclosure and installed system shall be acceptable to the local “authority having
jurisdiction,” as defined in the NEC, or “authorized person” as defined in the CEC.
2.1.3
Check Components
Verify that you have the correct redundant power supply components to meet your particular installation
requirements. The following table lists the available components for reference and the following figure
shows a typical installation configuration.
Note that model numbers beginning with the prefix “TK” are for a coated version of the component.
Model Number
Component
Quantity per Chassis
TC-RPCXX1 or
TK-RPCXX1
120/240Vac Redundant Power
Supply
2
1
TC-RPDXX1 or
TK-RPDXX1
24Vdc Redundant Power Supply
2
1
TC-RPSCA2 or
TK-RPSCA2
Redundant Power Supply Chassis
Adapter
1
TC-RPSC04
Redundant Power Supply Cables
[Length is 914mm (3ft)]
2
User Supplied
2
12-14 AWG Annunciator Wiring
[Maximum Length is 10m (32.8ft)]
2
1.
The redundant power supply models can be mixed or matched, so the quantity would
be 1 per chassis if they were mixed.
2.
Optional user-supplied annunciator wiring can be connected to a solid-state relay for
status and troubleshooting purposes.
ATTENTION
If you have a Series A chassis with any of the following model numbers, contact your Honeywell
Service representative for redundant power supply options.
l
TC-FXXnn1
l
TK-FXXnn1
Note: nn = the number of slots available in the chassis, (04, 07, 10, 13, 17).
- 6 -
Chapter 2 - Installation