Chapter 2 - Installation
6. Observing spacing and layout recommendations, repeat this procedure to install the other
redundant power supply (ies).
ATTENTION
Be sure the power supply is mounted and all panel fabrication is completed before you
remove the protective label. The label protects the power supply from metal shavings
falling inside it.
7. Peel the protective label off the top of each redundant power supply.
8. Go to the next section
Installing redundant power supply chassis adapter
2.2.2
Installing redundant power supply chassis adapter
Use the following procedure to install a chassis adapter on the left most side of a chassis.
1. Align the right side of the chassis adapter with the left most edge of the chassis.
- 13 -