Chapter 2 - Installation
Figure 2.1 Typical Redundant Power Supply Application
The redundant power supplies (TC-RPCxx1 or TC-RPDxx1) are surface mounted within 3 feet of the
controller or I/O chassis. A redundant power supply adapter, (TC-RPSCA2) is installed on one end of
the chassis. Three-foot cables, (TC-RPSC04) are installed connecting the redundant power supplies to
the adapter.
2.1.4
Verify mounting space requirements
ATTENTION
Be sure you meet these minimum spacing requirements when mounting components in an
enclosure, as shown in the following Figure.
l
10.2cm (4in) between redundant power supplies and the enclosure.
l
2.55cm (1in) between redundant power supplies.
l
15.3cm (6in) between chassis and heat source.
l
5.1cm (2in) between wireway and top or bottom of chassis.
l
5.1cm (2in) between wireway and power supply.
l
7.7 to 10.2cm (3 to 4in) between chassis mounted horizontally - not shown.