background image

CAuTION:  Do  not  loop  wire 
under  terminal  1  or  2.  Break 
wire run to provide supervision 
of connections.

H500-32-00 

I56-1982-004R

Figure 4. Replacing the filter cover:

Figure 3. Test magnet position:

Figure 2. Rotary decade address switches:

C0162-00

A detector that fails any of these tests should be retested. If the 
detector still fails any test, have its filter replaced (see instructions 
below) and retested. Finally, if the detector continues to fail after 
replacing the filter, it must be returned for repair or replacement.
When testing is complete, restore the system to normal opera-
tion and notify the proper authorities that the system is back 
in operation.
TESTINg
The unique design of Filtrex eliminates the need for typical detector 
cleaning. The  only  maintenance  necessary  is  replacing  the  filter, 
which is signaled by a trouble condition at the panel (see below).
Filtrex has been designed to maximize the amount of time before 
maintenance  is  required.  Filtrex  utilizes  a  replaceable  filter  that 
may become clogged over time. Filtrex detector monitors itself to 
insure that the filter has not become clogged. Because environ-
mental conditions can vary significantly, the amount of time before 
maintenance could vary significantly as well. To fully understand 
maintenance requirements of Filtrex in its installed location, it is 
recommended that the following test program be conducted.
1.  Install the Filtrex detector in the desired location.
2.  Connect the Filtrex detector to the fire alarm control panel.
3.  Maintain  a  record  for  at  least  90  days  of  any  maintenance 

performed on or required by Filtrex.

4.  At the end of the test period, use the record to develop and 

schedule maintenance. Filtrex should be serviced at regular 
intervals  to  insure  that  the  fire  alarm  system  provides  con-
tinuous protection.

REPlACINg THE FIlTER
IMPORTANT:
 When the filter becomes too clogged to draw ade-
quate air into Filtrex, power is automatically cut from the detector, 
sending a trouble signal to the fire control panel. After 5 minutes, 
power  is  restored  to  the  detector  for  72  hours. After  72  hours, 
power is cut again and the detector will remain off-line until the 
filter is replaced. 
NOTE: The unit has two filters. The replaceable filter is inside the 
cover. A permanent filter is mounted to the unit.

H500-32-00 

I56-1982-004R

Figure 1. Wiring diagram:

WIRINg INSTRuCTIONS
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of 
the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mis-
takes and ease system troubleshooting. Improper connections will prevent a system from responding properly in the event of a fire.
NOTE: Although the TC844A1015  is an intelligent sensor, a separate pair of wires is required for power. This power must be provided 
from a listed fire alarm power supply.
Remove power from the communication line before installing detectors.
All wiring must conform to applicable local codes, ordinances, and regulations.
1.  Wire the sensor base per the wiring diagram, please see Figure 1.
2.  Set the desired address on the sensor address switches, please see Figure 2.
 

NOTE: Some panels support extended addressing. In order to set the sensor above address 99 on compatible systems, carefully 
remove the stop on the upper rotary switch with thumb as shown in Figure 2.

3.  Insert 5-wire connector on mounting base into 5-pin connector on Filtrex unit. Install the detector into the sensor base. Push the 

detector into the base while turning it clockwise to secure it in place. (Please see Figure 5 and INSTALLING FILTREX INTO BASE 
on page 4 for specific directions.

4.  After all detectors have been installed, turn on the detector power supply, then apply power to the control unit and activate the 

communication line.

5.  Test the detector(s) as described in the TESTING section of this manual.

CAUTION

Dust cover must be removed before the detector can sense smoke. 

TESTINg
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable 
the system to prevent unwanted alarms.
All detectors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority Having Jurisdiction 
(AHJ). Detectors offer maximum performance when tested and maintained in compliance with NFPA 72. 
The sensor can be tested in the following ways:
A.  Functional: Magnet Test (P/N M02-04-01 or M02-09-00) 
 

This detector can be functionally tested with a test magnet. The test magnet electronically simulates smoke in the sensing cham-
ber, testing the detector electronics and connections to the control panel.

 

1.  Hold the test magnet in the magnet test area as shown in Figure 3.

 

2.   The detector should alarm the panel. Two LEDs on the detector are controlled by the panel to indicate sensor status. Coded 

signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel technical 
documentation for detector LED status operation and expected delay to alarm.

B.  Smoke Entry: Aerosol generator 
 

Aerosol generators for smoke entry testing are available from a number of third party manufacturers (e.g., Gemini Scientific). Fol-
lowing the manufacturer’s instructions, apply aerosol until the panel alarms.

TEST MAGNET
MARKER

Cover is keyed to 
fit into 4 matching 
sized slots.

 

Alignment marks 
are provided on the 
cap and top of the 
permanent filter. 

 

LISTED COMPATIBLE CONTROL PANEL

AUX.

POWER
SUPPLY

+

+

AUX

+

AUX

AUX

+

AUX

2(–) 3(R

A) 4(S)

1(+)

1(+)

2(–) 3(R

A) 4(S

)

TENS

Breakaway Stop

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

C0845-00

C0191-00

C0121-00

C0190-00

Reviews: