background image

THE ROUND® CREATIVE SERIES Y460A2003 THERMOSTAT

3

69-1358

Firmly tighten the screws.

Push the excess wire back into the wall.

Plug the hole with nonflammable insulation to 
prevent drafts from affecting the thermostat 
operation.

Y460A for heating/cooling system using separate RC-
RH terminals. If old thermostat has single R terminal, 
refer to jumper drawing in Subbase Wiring procedure.

6 MOUNT YOUR THERMOSTAT

Set the heat anticipator indicator to 1.2 before 
mounting to prevent the anticipator from burning out 
during installation.

Align the thermostat over the subbase and tighten 
the three captive mounting screws (see Step 4). 
These captive mounting screws complete the 
electrical connections to the thermostat.

7 SET HEAT ANTICIPATOR 
INDICATOR

Be sure the thermostat adjustable heat anticipator is 
set correctly to accurately control the temperature.  
An incorrect setting (if too high) can result in wide 
room temperature swings or (if too low) burn out the 
anticipator, which voids the thermostat warranty.

Make sure you have the current draw (anticipator 
setting) for your system. This is the number you 
wrote in the box in Step 3. If you were unable to find 
the current draw for Step 3, this information can be 
found printed on the primary control at the furnace or 
boiler. The primary control is usually a gas valve, a 
relay or burner control box, Aquastat® Controller or 
zone valve with the thermostat wires connected to it. 
These controls are usually located behind the 
furnace cover; see the illustration. 

If the current rating is still unavailable:

— Remove the W wire from the subbase.

— Connect one probe of an ac ammeter (0 to 2.0A, 

for example) to the W wire and connect the other 
probe to the W terminal.

R

G

R

W

Y

EXAMPLE:  FOR RC TO RH 
JUMPER,  STRIP WIRE 
END LONG ENOUGH TO 
JOIN BOTH TERMINALS.

M1277A

H

C

M13418

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.

IN HEATING, THE FAN IS CONTROLLED BY ANOTHER CONTROLLER, 
SUCH AS A HONEYWELL L4064 FAN AND LIMIT CONTROLLER OR 
FAN TIMER.

1

1

1

COOL

HEAT

O

F

F

FAN

ON

AUTO

G

R

R

H

Y

W

C

HEATING 
RELAY OR
VALVE COIL

COOLING
CONTACTOR
COIL

FAN
RELAY

2

LONGER

.15

.12

.2

.6

.8

1.0

.5

.4

.3

HOLE SUITABLE FOR 
PENCIL POINT 
TO MOVE INDICATOR

HEAT 
ANTICIPATOR
INDICATOR

SCALE

M1368

V8043E 1004 4
24V 50/60CY

.32 AMP @ 60CY

8406 

24 Vac 50/60 Hz

0.4 AMP

30 VAC

0.2

 A

M

P

T

F

T

F

OIL BURNER CONTROL

SHOWS
CURRENT 
DRAW

SHOWS 
VOLTAGE
RATING

M6116B

FROM MAIN
FUEL SUPPLY

SHOWS
VOLTAGE
RATING

TO
BURNER

SHOWS
ANTICIPATOR
SETTING

TYPICAL GAS VALVE

ZONE VALVE

SHOWS
VOLTAGE
RATING

SHOWS
ANTICIPATOR
SETTING

Summary of Contents for THE ROUND Y460A2003

Page 1: ...MOSTAT Carefully unpack your new thermostat Remove and discard the shipping wrap be sure to save the screws and the instructions Remove the thermostat cover and set it aside to use later Remove the red plastic insert that holds the mercury switch in place 3 REMOVE YOUR OLD THERMOSTAT Remove the cover of the old thermostat If the cover does not snap off when pulled firmly from the bottom look for s...

Page 2: ... outlet box with the mounting screws as shown in the illustration Tighten the screws after using a spirit level or plumb line to accurately level the subbase It must be level to maintain accurate calibration 5 WIRE THE SUBBASE Follow the instructions provided by the heating or heating cooling equipment manufacturer If not available refer to the thermostat wiring diagram NOTE All wiring must comply...

Page 3: ...tep 3 this information can be found printed on the primary control at the furnace or boiler The primary control is usually a gas valve a relay or burner control box Aquastat Controller or zone valve with the thermostat wires connected to it These controls are usually located behind the furnace cover see the illustration If the current rating is still unavailable Remove the W wire from the subbase ...

Page 4: ...ge Hazard Can cause permanent damage to the compressor or other equipment To avoid possible compressor damage allow the compressor to remain off for five minutes before restarting To avoid possible equipment damage do not operate cooling when the outside temperature is below 50 F 10 C See equipment manufacturer instructions CAUTION Equipment Damage Hazard Can cause permanent damage to the compress...

Page 5: ...YWELL MAKES ON THIS PRODUCT THE DURATION OF ANY IMPLIED WARRANTIES INCLUDING THE WAR RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE IS HEREBY LIMITED TO THE ONE YEAR DURATION OF THIS WARRANTY Some states do not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you This warranty gives you specific legal rights and you may have other ri...

Page 6: ... Mexico www honeywell com Home and Building Control Home and Building Control Honeywell Inc Honeywell Limited Honeywell Limitée Honeywell Plaza 155 Gordon Baker Road P O Box 524 North York Ontario Minneapolis MN 55408 0524 M2H 3N7 ...

Reviews: