User Settings
TP1MAN Issue 3 Apr 06 (MAN0630)
43
8
Press OK to accept the change.
The display now changes to the current A2 Alarm 2 setting.
5
Press OK to accept the change.
The display changes to the A1 relay action menu.
The display shows either r 1-d (for relay 1 de-
energized), or r 1-E (for relay 1 energized).
6
Use Up/Down to change the relay action.
7
Press OK to accept the change.
The display changes to the relay latching or non-
latching menu and shows either r 1-L (for Relay 1
latching), or r 1-N (for Relay 1 non-latching).
Use Up/Down to change the relay action.
The diagram shows the effect of latching or non
latching relays.
Flashing visual indicators
show alarm has occurred
and not
pressed
Cancel
Alarm Point
Alarm Relay
Operation
(Latching)
Alarm Relay
Operation
(Non-Latching)
Audible Alarm
Visual Alarm
Gas Reading Press
button Press
button
Cancel Cancel
Visual alarm not cleared
until gas alarm has
cleared and
pressed
Cancel is
Visual indicators stop f
pressed
but gas still present
lashing
and go steady when Cancel
Audible alarm can be
silenced with gas present
If gas rises again then
Audible Alarm re-activates