User Settings
TP1MAN Issue 3 Apr 06 (MAN0630)
46
mV input detector
4-20 mA input detector
* User configurable alarm set point in the range 10% to 90% of full scale.
Function
Default Configuration
Display range and units
0-100% LEL
mV Signal
<2.9 mV
Fault (open circuit)
2.9 - 3.5 mV
Normal operation
>3.5 mV
Overrange
Alarm Relay 1*
Alarm level 1 — 20% LEL
Latching, normally de-energized, energizes on alarm
(Single Pole Change Over 240 Vac 3A max)
Alarm Relay 2*
Alarm level 2 — 40% LEL
Latching, normally de-energized, energizes on alarm
(Single Pole Change Over 240 Vac 3A max)
Fault Relay
Non-latching, normally energized, de-energizes on fault
(Single Pole Change Over 240 Vac 3A max)
Function
Default Configuration
Display range and units
0-100% FS
mA Signal
0 - 1.5 mA
Open circuit fault
1.5 - 2.5 mA
Inhibit
2.5 - 3.2 mA
Drift fault
3.2 - 4.0 mA
Deadband
4.0 to 20.0 mA
Normal operation
22.0 mA
Max. overrange
Alarm Relay 1*
Alarm level 1 — 20% of full scale
Normally de-energized, energizes on alarm
(Single Pole Change Over 240 Vac 3A max)
Alarm Relay 2*
Alarm level 2 — 40% of full scale
Normally de-energized, energizes on alarm
(Single Pole Change Over 240 Vac 3A max)
Fault Relay
Non-latching, normally energized, de-energizes on fault
(Single Pole change over 240 Vac 3A max)