Specifications
TP1MAN Issue 3 Apr 06 (MAN0630)
53
Inputs
Outputs
Supply
85-265Vac, 50/60Hz auto-sensing, 18-32 Vdc, maximum power 30 Wac and/
or 15Wdc
Detector Type
3 wire mV bridge
2 wire, 4-20 mA,
loop powered
3 wire, 4-20 mA,
source output
Example
Sensepoint Flammable
Sensepoint Toxic
and Oxygen
Sensepoint Plus
and Sensepoint Pro
Detector
Supply
mV Bridge Input Module
Constant current supply: 200 mA
Self regulating supply voltage
subject to cable resistance
Maximum loop resistance: 18 Ohms
mA Input Module
Maximum detector current supply: 500 mA
Minimum guaranteed supply voltage
from the controller: 18 Vdc
input impedance: 100 Ohms
Relays
Alarm 1 (A1)
Alarm 2 (A2)
Fault (F)
Rating
SPCO/3 A, 240 Vac (non inductive load)
Default
Settings
Latching
Non- Latching
De-energized Energized
Energize on alarm
De-energize on fault or
loss of power
Factory setting 20% FS Factory setting 40% FS
User
Configurable
Options
Latching/non-latching
Energized/de-energized
Rising/falling (oxygen only)
Trip point 10-90% FS