Operation
TP1MAN Issue 3 Apr 06 (MAN0630)
33
Cancelling Operations/Choices
To cancel operations/choices:
Press the
— Cancel — button.
This returns to the previous menu level, setting, etc.
Pressing Cancel again returns to normal operation.
Note
The system automatically returns to normal operation if no buttons are pressed for
more than 30 minutes.
For details of the Common Module menu see page 37. For details of the Channel Module menu
see page 43. To change user settings/configuration using the menus and control buttons see
Alarms
When any detector event occurs, e.g.
Alarm 1
,
Alarm 2
or
Fault
, the following occurs:
•
the status icon for the event flashes, e.g.
— for Alarm 1
•
the LED for the type of event flashes, e.g.
— ALARM
•
the audible alarm sounds
To acknowledge/accept any alarm press the
Cancel
button.
This silences the audible alarm and at the same time the related icon and LED on the display
change from flashing to steady.
For detailed operation of audible and visual alarms under latching/non latching relay
configuration refer to page
Pressing the
Cancel
button when there are no alarms/faults tests the display and visual
indicators, without operating the alarm relays.