background image

TP790 AND TP9600 SERIES PNEUMATIC THERMOSTATS

3

77-9382—1

Fig. 2. Cross Section of TP970 and TP9600 Thermostat Showing Valve Unit and Airflow.

Figure 4 shows the valve unit supplying air to the branch
line. This condition occurs when the bimetal sensing element
forces the Thermostat flapper toward the nozzle, decreasing
the nozzle-flapper gap and increasing the pilot pressure.

The increased pilot pressure against the pilot diaphragm
overcomes the force of the BLP on the branchline
diaphragm. This change opens the valve unit at Point B,
allowing main air to flow into the branch line. BLP builds until
the pressure against the branch diaphragm again equals the
pressure against the pilot chamber diaphragm. The main
airflow then shuts off, bringing the valve unit into a balanced
condition at a new pressure.

With direct-acting bimetal sensors, a temperature increase
closes the nozzle-flapper gap; with reverse-acting bimetal
sensors, a temperature increase opens the nozzle-flapper
gap. The arrows in the air passages in Figure 4 show the
direction of airflow.

C6047-1

FLAPPER

BIMETAL

FILTER

RESTRICTOR

BRANCH LINE

THROTTLING RANGE
ADJUSTMENT 

CALIBRATION

SCREW

SETPOINT
CAM

SETPOINT
KNOB

NOZZLE

BRANCHLINE

PRESSURE TAP

BRANCHLINE

CHAMBER

BLEED

PILOT 

PILOT

CHAMBER

EXHAUST

VALVE

MAIN

LINE

TP970, TP9600, TP971, TP9610, TP972, and TP9620
Thermostats are designed around a valve unit for flow
amplification rather than conventional pressure amplification.
Branchline chamber and pilot chamber design are such that
branch pressure is equal to nozzle pressure at a higher
capacity.

Figures 3, 4, and 5 are cross-sections of the valve unit only,
showing air passages and the pilot-branch diaphragm
relationship.

Figure 3 shows a valve unit in a strategic or balanced
condition. All the forces are equal; BLP equals the pilot-line
pressure.

No main air enters the branchline chamber and no exhaust
air leaves the branchline chamber. In this static condition,
the valve is sealed at both Points A and B, preventing airflow.

Fig. 3. Valve Unit Flow Amplifier in a

Balanced (Static) Condition.

PILOT CHAMBER

EXHAUST

BRANCH

CHAMBER

POINT A

POINT B

MAIN LINE

BRANCH

LINE

VALVE

PILOT AIR

C6048-1

Fig. 4. Valve Unit Shown with Pilot

Chamber Pressure Increased.

POINT A

EXHAUST AIR

POINT B

MAIN LINE

BRANCH
LINE

PILOT AIR

C6049-1

NOTE:  THE SEAL AT POINT A DOES NOT

ALLOW AIR TO EXHAUST.  

VALVE

Summary of Contents for TP9600 Series

Page 1: ...ts 4 General 4 Operation 5 Direct Action 5 Reverse Action 5 TP970A D and TP9600A B High Capacity Single Temperature Thermostats 6 General 6 Operation 6 Direct Action 6 Reverse Action 7 TP971A C and TP9610A B High Capacity Dual Temperature Thermostats 7 TP971B and TP9610B 7 TP971C 7 TP971A and TP9610A 7 Daytime Operation 8 Nighttime Operation 8 Manual DAY Override 9 TP972A and TP9620A High Capacity...

Page 2: ... a fixed branchline pressure BLP for each temperature within the temperature and throttling range settings The forces within the nozzle flapper bimetal assembly always seek a balanced condition giving the same BLP for the same temperature regardless of fluctuations in main air or the relative positions of the nozzle flapper and bimetal Flapper Nozzle Operation Flapper nozzle operation is generally...

Page 3: ...METAL FILTER RESTRICTOR BRANCH LINE THROTTLING RANGE ADJUSTMENT CALIBRATION SCREW SETPOINT CAM SETPOINT KNOB NOZZLE BRANCHLINE PRESSURE TAP BRANCHLINE CHAMBER BLEED PILOT PILOT CHAMBER EXHAUST VALVE MAIN LINE TP970 TP9600 TP971 TP9610 TP972 and TP9620 Thermostats are designed around a valve unit for flow amplification rather than conventional pressure amplification Branchline chamber and pilot cha...

Page 4: ... operation is very important to understanding TP970 TP9600 TP971 TP9610 TP972 and TP9620 operation As can be seen from Figures 3 4 and 5 pilot pressure changes affect BLP changes in the same ratio There is no pressure gain to amplify errors as with other pneumatic Thermostats Still the main air supply being switched through the valve unit provides fast high capacity increase and decrease of BLP TP...

Page 5: ... the bimetal are again in equilibrium with the opposing force 8 psi 55 kPa times the area of the nozzle at the flapper A reduction in setpoint causes the reverse to happen The calibration screw allows for matching the bimetal start position with the indicated setting on the setpoint cam to achieve an 8 psi 55 kPa BLP at the indicated setpoint The TR adjustment Fig 9 provides a means for changing t...

Page 6: ...reater temperature change at the bimetal to throttle the flapper over the nozzle The result is a wider TR or very low sensitivity for instance a 1 F 0 56 C change in temperature results in only a 1 psi 7 kPa BLP change TP970A D AND TP9600A B HIGH CAPACITY SINGLE TEMPERATURE THERMOSTATS General The TP970 and TP9600A B Thermostats Fig 10 are the basic TP973 with a valve unit added for greater capaci...

Page 7: ... TP9610A On the TP971A and TP9610A direct acting Thermostats Fig 12 the daytime bimetal controls the system when the main air pressure is 13 psi 90 kPa The nighttime element controls the system when the main air pressure reaches 18 psi 124 kPa Models are available with switchover pressures of 16 to 21 psi 110 to 145 kPa and 20 to 25 psi 138 to 172 kPa Fig 12 TP971 and TP9610 Day Night Thermostat T...

Page 8: ...and TP9610 Operation on Day Cycle Main Air Pressure 13 psi 90 kPa Nighttime Operation In Figure 14 the main air pressure is at 18 psi 124 kPa for nighttime operation The airflow shown by arrows is the same as the daytime cycle up to Logic Module A and Logic Module B The main air pressure 18 psi 124 kPa is now enough to overcome the spring loaded diaphragm in Logic Module A Because the manual overr...

Page 9: ...ic switchover The secondary branch line operates with the manual DAY AUTO lever position as follows 1 System in normal daytime operation 13 psi 90 kPa main air pressure Fig 13 dotted lines 2 Move the manual DAY AUTO lever to the DAY position It snaps back to AUTO because there is no air pressure on logic switch C Fig 13 The secondary branch line is always at the main air pressure when the system o...

Page 10: ... the system to normal operation by manually switching the DAY AUTO lever to AUTO In the preceding situation the P E switch contacts are closed This is because the secondary BLP is under 15 psi 103 kPa the DAY AUTO lever is held in the DAY position by pressure on Logic Module C and the Thermostat uses its daytime bimetal because the airflow through Logic Module D is closed off TP972A AND TP9620A HI...

Page 11: ...rride and the independent setpoint adjustment Cooling control requires a lower pressure in the main air supply Figure 17 shows the workings and traces the air path within the TP972A and TP9620A when it is controlling with the cooling bimetal NOTE The TP972A2036 A2168 and A2176 and TP9620A limited control range Thermostats have separate concealed setpoints for heating and cooling and limit the heat...

Page 12: ... the Module The air pressure is applied to the diaphragm of Logic Module B closing off Port B1 and opening Port B2 Now the air is directed to the flapper nozzle of the heating bimetal and the Thermostat controls in the heating mode TP974A ROOM TEMPERATURE SENSOR General The TP974A Fig 19 20 is a bimetal element proportioning temperature sensor for either two or one pipe applications The sensor bim...

Reviews: