Q7100A,C,D

Thermostat Subbases

APPLICATION

The Q7100 Thermostat Subbases provide electronic
control of commercial 24 Vac single or multistage heat
pump or conventional heating and cooling systems.
Select models have terminals for light emitting diodes
LEDs, remote temperature sensors and remote setback
timer. The LED models  have up to two field configurable
LEDs and up to two factory assigned LEDs. Refer to
Table 1. All Q7100 Thermostat Subbases require a
common wire to the supply power.

Table 1. Description of Q7100 Subbases.

Use  

Stages

a

Q7100 T7100

System

Heat  

Cool  

Figs.

A

D or F Conventional

1 or 2

1 or 2

8-9

C

E or F Heat pump

1, 2 or 3 1 or 2

10-14

D

E or F Heat pump

1 or 2

1 or 2

15

a

Depends on the model.

RECYCLING NOTICE

If this control is replacing a control that contains
mercury in a sealed tube, do 

not place your old

control in the trash.

Contact your local waste management authority
for instructions regarding recycling and the proper
disposal of the old thermostat.

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow

the instructions can damage the product or cause
a hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After completing installation, use these instructions

to check out the product operation.

CAUTION

Disconnect power supply to prevent electrical
shock or equipment damage.

Location

Subbase without Remote-Mounted Temperature Sensor

Install the subbase about 5 ft (1.5m) above the floor in an
area with good air circulation at average temperature.
See Fig. 1.

Do not install the subbase where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

Subbase with Remote-Mounted Temperature Sensor(s)

Install the subbase in an area that is accessible for
setting and adjusting the temperature and settings.

Install the remote-mounted sensor(s) about 5 ft (1.5m)
above the floor in an area with good air circulation at
average temperature. See Fig. 1.

Do not mount the sensor(s) where it can be affected by:

drafts, or dead spots behind doors and in corners.

hot or cold air from ducts.

radiant heat from sun or appliances.

concealed pipes and chimneys.

unheated (uncooled) areas such as an outside wall
behind the thermostat.

If more than one remote sensor is required, they must be
arranged in a temperature averaging network consisting
of two, three, four, five or nine sensors. See Fig. 2
through 6.

69-0931-3

Summary of Contents for TRADELINE Q7100A

Page 1: ...ions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation CAUTION Disconnect power supply to prevent electrical shock or equipment damage Location Subbase without Remote Mounted Temperature Sensor Install the subbase about 5 ...

Page 2: ...iding a temperature averaging network for a T7100 Q7100 Thermostat Subbase M4838 T T SUBBASE T T T7047G T7047G T T M4839 T T SUBBASE T T T7047C T T T7047C T T T7047G M4840 T T T T SUBBASE T7047C T T T7047C T T T7047C T T T7047C Fig 4 Four T7047C Sensors providing a temperature averaging network for a T7100 Q7100 Thermostat Subbase M4841 T T SUBBASE T T T7047G T T T7047G T T T7047G T T T7047G T T T...

Page 3: ... to Fig 9 through 15 for typical hookups A letter code is located near each terminal for identification CAUTION Disconnect power before wiring to prevent electrical shock or equipment damage 1 Loosen the terminal screws on the back of the thermostat and connect the system wires See Fig 8 IMPORTANT Use 18 gauge color coded thermostat cable for proper wiring 2 Securely tighten each terminal screw 3 ...

Page 4: ...ELAY 1 Y2 RH T D REMOTE TEMPERATURE SENSOR HEAT RELAY 2 W1 B T COMPRESSOR CONTACTOR 2 HEAT DAMPER L1 HOT L2 2 COMPRESSOR CONTACTOR 1 3 2 3 REMOTE SETBACK TIMER L1 HOT L2 M11089 COMPRESSOR CONTACTOR FAN RELAY O G Y1 COOL CHANGEOVER VALVE HEAT CHANGEOVER VALVE SUBBASE X HEAT RELAY AUX HEAT RELAY EM HT RELAY W1 R T T D D SENSOR TIMER EQUIPMENT MONITOR X1 E B W2 L1 HOT L2 POWER SUPPLY PROVIDE DISCONNE...

Page 5: ... temperature sensor and remote setback timer L1 HOT L2 M4834B FAN RELAY D O E W3 Y2 COOL CHANGEOVER VALVE SUBBASE 2 X B G EM HT RELAY R T D REMOTE TEMPERATURE SENSOR AUX HT RELAY Y1 T COMPRESSOR CONTACTOR 2 CAUTION EQUIPMENT DAMAGE WILL OCCUR IF POWER IS CONNECTED TO THE D TERMINALS POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED SELECT MODELS HAVE LEDS X4 NEEDS TO BE JUM...

Page 6: ...Home and Building Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 2C9 69 0931 3 Rev 2 98 L C Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 www honeywell com ...