background image

62-0131—2

4

Q7300L SERIES 2000 COMMERCIAL THERMOSTAT SUBBASE

WIRING SUBBASE

All wiring must comply with local electrical codes and ordinances. Follow equipment manufacturer wiring instructions when
available. Refer to Fig. 9 and 10 for typical hookups. A letter code is located near each terminal for identification. See
Table 3 for terminal descriptions and system action.

Table 3. Terminal Descriptions and Conditions.

CAUTION

Disconnect power before wiring to prevent
electrical shock or equipment damage.

1. Loosen the terminal screws on the subbase and

connect the system wires. See Fig. 8.

IMPORTANT

Use 18-gauge, solid-conductor color-coded
thermostat cable for proper wiring. If using 18-
gauge stranded wire, no more than ten wires can
be used. Do not use larger than 18-gauge wire.

2. Securely tighten each terminal screw.
3. Push excess wire back into the hole.
4. Plug the hole with nonflammable insulation to

prevent drafts from affecting the thermostat.

NOTE: After wiring, check that all connections are tight

and secure. See Fig. 8. Loose or intermittent wire
connections cause inconsistent system operation.

Standard Terminal

Designations

Typical Connection

Function

Terminal Type

A1, A2

Damper Control Relay.

input, output

24V powered

contact

BM

ML7984 Actuator connection. No call for heat, valve
closed during occupied periods and open during
unoccupied periods.

output

C1, C2, C3, C4, C5

Communication input for T7147.

FC

Fan control Transformer.

input

GH

High speed fan output. Activated during calls for cooling.

output

24V powered

contact

GL

Low speed fan output. Activated on calls for heat and
fan On selection.

output

24V powered

contact

P1, P2

Pump Interlock Relay. Operates circulator pump in
hydronic heat or energizes conventional heat system.

input, output

24V powered

contact

R

24V System Transformer

input

RM

ML7984 Actuator connection. No call for heat, valve
closed. Call for stage 1 heat, valve approximately one-
half open. Call for stage 2 heat, valve fully open.

T, T

Remote sensor input for T7047 or T7147.

X

Heating transformer common

input

Y

Cool call

24V output on Y

Fig. 8. Proper wiring technique.

M4826

FOR WRAPAROUND
INSERTION STRIP
7/16 IN. (11 MM).

FOR STRAIGHT
INSERTION STRIP
5/16 IN. (8 MM).

Summary of Contents for TRADELINE Q7300L

Page 1: ...ximum at 30 Vac 50 or 60 Hz Output Relay Current See Table 2 Table 2 Maximum Amps at 30 Vac Temperature Ratings Operating Ambient 40 F to 110 F 4 C to 43 C Shipping 30 F to 150 F 34 C to 65 C Display Accuracy 1 F 0 5 C Setpoint Range 45 F to 95 F 7 C to 35 C Differential 2 F 1 C Humidity Ratings 5 to 90 RH noncondensing RECYCLING NOTICE If this control is replacing a control that contains mercury ...

Page 2: ...e mounted sensor s about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not mount the sensor s where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat If more than o...

Page 3: ...emperature averaging network for T7300 Q7300 Thermostat Subbase Mounting Subbase The subbase mounts horizontally on the wall or a 2 in x 4 in wiring box Position the subbase horizontally on the wall or on a 2 in x 4 in wiring box 1 Position and level the subbase or wallplate for appearance only The thermostat functions properly even when not level 2 Use a pencil to mark the mounting holes See Fig ...

Page 4: ...ns are tight and secure See Fig 8 Loose or intermittent wire connections cause inconsistent system operation Standard Terminal Designations Typical Connection Function Terminal Type A1 A2 Damper Control Relay input output 24V powered contact BM ML7984 Actuator connection No call for heat valve closed during occupied periods and open during unoccupied periods output C1 C2 C3 C4 C5 Communication inp...

Page 5: ... CA3 CA5 A2 COOLING RELAY X P2 P1 BM LOW SPEED FAN RELAY DAMPER CONTROL RELAY PUMP INTERLOCK RELAY 3 9 3 4 7 5 6 7 8 9 8 4 6 HIGH SPEED FAN RELAY ML7984 VALVE ACTUATOR R1 B3 W T5 T6 5 TRANSFORMER FAN TRANSFORMER AS AS DISCHARGE AIR SENSOR CONNECT GND TO EARTH GROUND DISCHARGE AIR SENSOR IS ONLY COMPATIBLE WITH T7300F THERMOSTAT JUMPER GH AND GL FOR SINGLE SPEED FAN SET THE DIP SWITCHES ON THE ML79...

Page 6: ...ess lower edge of case to latch NOTE To remove the thermostat from the wall first pull out at the bottom of the thermo stat then remove the top IMPORTANT Refer to the thermostat installation instructions for Installer Setup Settings Installer System Test and Troubleshooting information Fig 11 Mounting thermostat on subbase M4824A B PRESS LOWER EDGE OF CASE TO LATCH A ENGAGE TABS AT TOP OF THERMOST...

Page 7: ...s on last system If cool is the last system then call is for high speed fan When heat is the last system then call is for low speed fan GL or GH Occupied Heat Auto Stage 1 heat Heat LED activated In hydronic applications ML7984 approximately one half open Pump interlock relay activated to energize circulator pump In conventional applications stage 1 heat activated Low speed fan activated A2 GL RM ...

Page 8: ... Control Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 Helping You Control Your World 62 0131 2 J H Rev 7 97 www honeywell com building components Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 ...

Reviews: