background image

2

Fig. 3—Typical hookup for Tradeline R8184G with indicator light and isolated alarm relay.

2. Safety switch should lock out in safety switch timing

(see label). Indicator light should come on. Ignition and
motor should stop and oil valve should close.

Simulate power failure:
1. Follow starting procedure to turn on burner.
2. With burner running, trip circuit breaker or remove

fuse to turn off power to the system.

3. Burner should stop.
4. Restore power. Burner should restart.
If system does not operate as described, proceed to

Troubleshooting.

TROUBLESHOOTING AND
MAINTENANCE

IMPORTANT

This control contains no field-serviceable parts. Do
not attempt to take it apart. Replace entire control if
operation is not as described.

PRELIMINARY STEPS

1. Check wiring connections and power supply. Make

sure power is on to the controls, burner motor, and ignition
transformer.

2. Make sure limit control is closed.

CHECK OIL PRIMARY RELAY
NOTE: You’ll need an insulated jumper wire with both ends

stripped.
1. Disconnect cad cell leads from F-F terminals.
2. Reset safety switch and set thermostat to call for heat.

Burner should start.

3. Within safety switch timing, jumper F-F terminals with

insulated jumper wire. Burner should continue to run.

4. After safety switch timing, remove jumper. Burner

should shut down in safety switch timing.

5. If operation is not as described, replace oil primary

control.

Mount control as shown in Fig. 1 or 2. After mounting,

make low voltage connections to the screw terminals. Strip
leads 3/8 in. [10 mm] and insert under terminal screw. See
Fig. 1 or 2. Connect cad cell leads to F-F terminals and
thermostat leads to T-T terminals. See Fig. 3 or 4.

CHECK SAFETY FEATURES

Simulate flame failure:
1. Follow starting procedure to turn on burner.
2. Close hand valve in oil supply line.
3. Safety switch should lock out approximately in safety

switch timing indicated on label. Indicator light should come
on. Ignition and motor should stop and oil valve should
close.

Simulate ignition failure:
1. Follow starting procedure to turn on burner, except do

not open oil supply hand valve.

CHECKOUT

START SYSTEM

WARNING

Fire hazard.
Can cause severe burns.
Make sure combustion chamber is free of oil or oil
vapor before starting system.
1. Push in and release red reset button.
2. Open hand valve in oil supply line.
3. Make sure system is powered. Check circuit

breaker or fuse and close system switch, if
provided.

4. Set thermostat to call for heat.
5. Burner should light and operate until call for

heat ends.

JUNCTION BOX

BLACK

L1
(HOT)

L2

LIMIT

BURNER
MOTOR

IGNITION

OIL VALVE
(OPTIONAL)

ORANGE

WHITE

BILATERAL
SWITCH

CAPACITOR

TRIAC

1K1

R2

R8184G PROTECTORELAY CONTROL

SAFETY
SWITCH

R1

1K2

M718

SAFETY
SWITCH 
HEATER

1K

CAD CELL

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

1

F

F

COOLING
CONTROL

2

LINE VOLTAGE 
THERMOSTAT

2

1

TO USE R8184 WITH LINE VOLTAGE CONTROLLER, JUMPER T-T TERMINALS AND CONNECT LINE 
VOLTAGE THERMOSTAT IN SERIES WITH LIMIT CONTROLLER.

3

T(W)

T(R)

LOCKOUT
INDICATOR
LED

SAFETY
SWITCH

R

G

Y

W

X

C

RH

FAN 
RELAY

L1 (HOT)

L2

1

2

3 REMOVE PLUG AND ROUTE VIOLET LEADWIRE THROUGH HOLE IN BASE OF R8184.

T87F/Q539A

COOLING
TRANSFORMER

VIOLET

Summary of Contents for TRADELINE R8184G

Page 1: ...991 Fig 1 Mounting the R8184G controls with 130 F 54 C maximum ambient temprature LOCATION 1 Mount on a 4 x 4 inch junction box directly on the main burner or inside the appliance cabinet In replacement applications mount in the same location as the old control 2 Ensure the operating temperatures are within the am bient temperature range Ambient temperature ranges are either 40 to 130 F 40 C to 54...

Page 2: ...s Strip leads 3 8 in 10 mm and insert under terminal screw See Fig 1 or 2 Connect cad cell leads to F F terminals and thermostat leads to T T terminals See Fig 3 or 4 CHECK SAFETY FEATURES Simulate flame failure 1 Follow starting procedure to turn on burner 2 Close hand valve in oil supply line 3 Safety switch should lock out approximately in safety switch timing indicated on label Indicator light...

Page 3: ...uts down the burner but doesnotdisconnectthepowersupply Turnoffpower at system switch or circuit breaker before servicing the control system burner motor oil valve or ignition to avoid electric shock To trip the safety switch move the safety switch lever down until the red reset button pops out and the indicator light comes on See Fig 5 Burner will not operate until safety switch is reset by pushi...

Page 4: ...omation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 www honeywell com ...

Reviews: