Specifications (continued)
External Static Pressure
Net Supply Air Flow
Gross Air Flow
Supply
Exhaust
Pa
in. W.C.
L/s
CFM
L/s
CFM
L/s
CFM
25
0.1
92
195
92
196
113
241
50
0.2
85
182
86
183
105
223
75
0.3
80
171
81
172
91
193
100
0.4
73
156
74
157
84
178
125
0.5
65
139
66
140
75
159
150
0.6
59
126
60
127
65
137
175
0.7
56
120
57
120
57
120
200
0.8
50
107
50
107
48
103
225
0.9
45
95
45
96
40
86
250
1.0
37
79
38
80
34
73
Supply Temperature
Net Supply Air Flow
Average
Power
Sensible
Recovery
Apparent
Sensible
°C
°F
L/s
CFM
Watts
Efficiency %
Effectiveness %
Heating
0
32
31
66
88
66
78
0
32
42
89
104
64
76
0
32
56
119
114
63
72
-25
-13
32
67
86
59
77
VNT5150H1000 Ventilation Performance
VNT5150H1000 Energy Performance
TrueFRESH™ ERV/HRV Ventilation Systems 69-2480EF—05
5
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0
50
100
150
200
250
0
25
50
75
100
125
150
175
200
0
10
20
30
40
50
60
70
80
90
100
110
AIR FLOW (CFM)
VNT5150H1000
AIR FLOW (L/S)
EXTERNAL
STATIC
PRESSURE
(PA)
EXTERNAL
STATIC
PRESSURE
(IN. W. C)
M32358
NET SUPPLY AIR FLOW