background image

TEMPERATURE SENSOR TYPE TS  

EN0H-1950GE23 R0410 

Honeywell GmbH • Subject to change without notice 

Function 

Due to temperature changes the resistance of temperature sensor will be changed. These change of resistance is changing proportional to the 
temperature and can be evaluated accordingly. 
 
Remarks: 

 

Select the appropriate temperature sensor with regard to scale range, performance and specific measurement conditions prior to instal-
ling and starting the refrigeration system. 

 

Please make sure that the temperature sensor is only used within the valid measuring range 

More Technical Details: 

Type 

TS – NFN 

TS – NFR 

TS – RFH 

Element Type 

NTC 10K 1% BETA 3435 

NTC 10K BETA 3977 tolerance ± 0,2 °C 

PT 1000 Class A 

Cable Type 

Thermical rubber poly. 

Thermical rubber poly.

 

Thermical rubber poly.

 

Cable colour 

Black 

Yellow 

Green 

Cable diameter 

2x0,25 mm² Ø 3,3 mm 

2x0,25 mm² Ø 3,3 mm 

2x0,25 mm² Ø 3,3 mm 

Connection Pins Pins 

Pins 

Filling 

Polyuretanic resin 

Polyuretanic resin 

Polyuretanic resin 

 

  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 
 
 

 

 
 

 
 

 

 
 
 

 

Type Description 

Temperature Sensor 

 TS 

 

NFN 

Type  

 

 

Type: 
NFN = NTC 10K 1% Beta 3435 
NFR = NTC 10K Beta 3977 ±0,2°C 
RFH = Pt 1000 class A 

 

   

 

Assembly 

 

Position the temperature sensor on the refrigerant pipe in the position between 10 and 14 o'clock (at horizontal pipe installation). 

 

Pay attention to install sensor to clean and intact surfaces at the measuring point. 

 

Provide sufficient thermal compound at the measuring point between temperature sensor and measuring surface. 

 

Fasten the temperature sensor by means of aluminum tape and/or fastening clips to the refrigerant pipe. 

 

Insulate the fastened temperature sensor with heat insulation material. 

 

Connect the temperature sensor according to the instructions of the evaluating equipment. 

 

Ensure that no humidity may enter at cable-ends. 

 

KAT-

T

S-

001

  

Manufactured for and on behalf of the  
Environmental and Combustion Controls  
Division of Honeywell Technologies Sàrl,  
1180 Rolle, Z.A. La Pièce 16, Switzerland  
by its Authorized Representative Honeywell GmbH 

Electrical Connections 

Connection of Temperature Sensors according below picture. Tempe-
rature Sensor is insensible against reverse polarity. TS Sensors have 
a 2-wire structure. To minimize electromagnetic perturbation the cable 
should be as short as possible. 

 

 

Automation and Control Solutions 
Honeywell GmbH 
Hardhofweg 
74821 Mosbach/Germany 
Phone: +49 

(0)

 

62

 

61

 

/

 

81-475 

Fax:    

+49 (0)

 

62

 

61

 

/

 

81-461 

E-Mail: cooling.mosbach@honeywell.com 
www.honeywell-cooling.com 

Reviews: