U2 COMBINATION VIEWING HEAD AND SIGNAL PROCESSORS
19
66-2071—02
40105
40115
40125
40135
40145
40155
40165
40175
UVSSGAIN
Solid state UV sensor gain setting for file 0
Solid state UV sensor gain setting for file 1
Solid state UV sensor gain setting for file 2
Solid state UV sensor gain setting for file 3
Solid state UV sensor gain setting for file 4
Solid state UV sensor gain setting for file 5
Solid state UV sensor gain setting for file 6
Solid state UV sensor gain setting for file 7
0
7
8 bit
40105
40116
40126
40136
40146
40156
40166
40176
UVSSFILT
Solid state UV sensor filter setting for file 0
Solid state UV sensor filter setting for file 1
Solid state UV sensor filter setting for file 2
Solid state UV sensor filter setting for file 3
Solid state UV sensor filter setting for file 4
Solid state UV sensor filter setting for file 5
Solid state UV sensor filter setting for file 6
Solid state UV sensor filter setting for file 7
0
7
8 bit
40107
40117
40127
40137
40147
40157
40167
40177
IRFILT
IR sensor filter setting for file 0
IR sensor filter setting for file 1
IR sensor filter setting for file 2
IR sensor filter setting for file 3
IR sensor filter setting for file 4
IR sensor filter setting for file 5
IR sensor filter setting for file 6
IR sensor filter setting for file 7
0
7
8 bit
40108
40118
40128
40138
40148
40158
40168
40178
IRGAIN
IR sensor gain setting for file 0
IR sensor gain setting for file 1
IR sensor gain setting for file 2
IR sensor gain setting for file 3
IR sensor gain setting for file 4
IR sensor gain setting for file 5
IR sensor gain setting for file 6
IR sensor gain setting for file 7
0
7
8 bit
40109
40119
40129
40139
40149
40159
40169
40179
OUTPUTGAIN
Current output gain for file 0
Current output gain for file 1
Current output gain for file 2
Current output gain for file 3
Current output gain for file 4
Current output gain for file 5
Current output gain for file 6
Current output gain for file 7
0
7
8 bit
40184
DISPLAYPAR
Various parameters.
Dim setting
(11 0000 000)
between 0 (dimmest)
and 24 (brightest).
Default=24.
Scroll type
(00 0000 0011) 0=no pause, 1=initial
pause, 2=end pause,
3=end pause
Scroll wait
(00 0001 1100) between 4 (short)
and 32 (long).
Default=16l
Scroll time
(00 1110 0000) between 0 (faster)
and 14 (slower).
Default=6.
0
4095
16 bit
40185
IWSENS
Touch wheel sensitivity (default is 5). The higher the value,
the more sensitive the touch wheel will be.
1
63
8 bit
40187
IWDATA
Output from touch wheel. When the wheel is touched, the
output increases from 0 to 127 as you move your finger
clockwise around the wheel. The output is 232 when no
touched. Write a 1 to re-calibrate the U2. Other numbers
will give an error. WARNING: DO NOT TOUCH THE
WHEEL WHILE RE-CALIBRATING.
0
255
8 bit
Table 5. Extended Modbus Register Map. (Continued)
Register
Name
Description
Minimum Maximum Size