U2 COMBINATION VIEWING HEAD AND SIGNAL PROCESSORS
66-2071—02
20
40189
PAGECNT
Counts every fourth time power is reset to the U2 (read
only)
-32768
32767
16 bit
40190
40191
40192
40193
40194
40195
40196
40197
40198
40199
IRFILTCOUNT
IR filter selection for filter 0 (read only)
IR filter selection for filter 1
IR filter selection for filter 2
IR filter selection for filter 3
IR filter selection for filter 4
IR filter selection for filter 5
IR filter selection for filter 6
IR filter selection for filter 7
IR filter selection for filter 8
IR filter selection for filter 9
-32768
32767
16 bit
40200
40201
40202
40203
40204
40205
40206
40207
40208
40209
UVFILTCOUNT
SSUV filter selection for filter 0 (read only)
SSUV filter selection for filter 1
SSUV filter selection for filter 2
SSUV filter selection for filter 3
SSUV filter selection for filter 4
SSUV filter selection for filter 5
SSUV filter selection for filter 6
SSUV filter selection for filter 7
SSUV filter selection for filter 8
SSUV filter selection for filter 9
-32768
32767
16 bit
40210 to 40219 IRSAVEDCNT
Saved exponential count of the IR filter when the auto-filter
routine was run. Registers correspond to Filter0 through
Filter9 (read only).
-32768
32767
16 bit
40220 to 40229 UVSAVEDCNT
Saved exponential count of the UV filter when the auto-
filter routine was run. Registers correspond to Filter0
through Filter9 (read only).
-32768
32767
16 bit
40230 to 40239 IRSAVEGAIN400
The gain at the IR filter to give a count of 400; used when
all 3 sensors are active to total a count of 1200. Saved at
the time the auto-filter routine was run. Registers
correspond to Filter0 through Filter9 (read only).
0
99
8 bit
40240 to 40249 IRSAVEDGAIN600
The gain at the IR filter to give a count of 600; used when 2
sensors are active to total a count of 1200. Saved at the
time the auto-filter routine was run. Registers correspond
to Filter0 through Filter9 (read only).
0
99
8 bit
40250 to 40259 IRSAVEDGAIN1200 The gain at the IR filter to give a count of 1200; used when
1 sensor is active to total a count of 1200. Saved at the
time the auto-filter routine was run. Registers correspond
to Filter0 through Filter9 (read only).
0
99
8 bit
40260 to 40269 UVSAVEDGAIN400 The gain at the UV filter to give a count of 400; used when
all 3 sensors are active to total a count of 1200. Saved at
the time the auto-filter routine was run. Registers
correspond to Filter0 through Filter9 (read only).
0
99
8 bit
40270 to 40279 UVSAVEDGAIN600 The gain at the UV filter to give a count of 600; used when
2 sensors are active to total a count of 1200. Saved at the
time the auto-filter routine was run. Registers correspond
to Filter0 through Filter9 (read only).
0
99
8 bit
40280 to 40289 UVSAVEDGAIN1200 The gain at the UV filter to give a count of 1200; used
when 1 sensor is active to total a count of 1200. Saved at
the time the auto-filter routine was run. Registers
correspond to Filter0 through Filter9 (read only).
0
99
8 bit
40290
TUBSAVECNT
Saved exponential count of the UV tube when the auto
filter routine was run (read only)
-32768
32767
16 bit
Table 5. Extended Modbus Register Map. (Continued)
Register
Name
Description
Minimum Maximum Size