 1 - CONFIGURATION OF THE CONTROL ALGORITHM 

Parameter Designation 

Unit 

Action: Direction 

of 

the control, direct or reverse acting. 

Typically, reverse control is used for heating and direct control for cooling applications. 

 

Proportional band: 

Proportional action is used to achieve stable control and is expressed as the percentage of the input span 
over which the output power level is directly proportional to the percentage of error between the PV and 
setpoint. 
Configurable from 0.0% (ON/OFF control) to 999.9%. 
WARNING: The 0.0% value sets the UDC100 to ON/OFF control irrespective of the other parameter settings 
e.g. integration and derivative times. 

in 0.1% increment 

Integration time: 

Integral action is used to eliminate any offset between the PV and SP due to proportional action. 
Integral time constant configurable from 0 second (OFF) to 5999 seconds. 
Setting the integral time to 0 will switch off the integral action. 
This parameter is ignored if the proportional band is set to 0.0% (ON/OFF control). 

in 1s increment 

Derivative time: 

Derivative action is used to return the PV back to the SP in a quicker time period after a process disturbance. 
The function is also utilized to limit the amount of overshoot of the PV during initial start up of a process. 
The operation of the derivative action is based on the rate of change of the PV with reference to the SP. 
Derivative time constant is configurable from 0 second to 5999 seconds. 
Setting the derivative time to 0 will switch off the derivative action. 
This parameter is ignored if the proportional band is set to 0.0% (ON/OFF control). 

in 1s increment  

Cycle time: 

Configurable up to 256s. WARNING : It is strongly recommended to avoid using cycle times below 
5 seconds, otherwise the precision of the output activation timing is not guaranteed. 

in 0.1s increment 

Max. rate: 

Maximum output increase between two consecutive input/output updates configured from 0% to 100%. 

in 0.1% increment 

Setpoint low limit: 

Configurable minimum setpoint value. 

in 1°C increment 

Setpoint high limit: 

Configurable maximum setpoint value. 

In 1°C increment 

Setpoint: Setpoint 

value used for control. 

in 1°C increment 

Output power high limit: 

Power output high limit configurable from 0 to 100% output. 

in 0.1% increment 

Output power low limit: 

Power output low limit configurable from 0 to 100% output. 

in 0.1% increment 

 

¾

 2 - SETTING THE PID PARAMETERS VIA THE UDC100 MMI 

In normal operating conditions, the upper display shows the process variable [PV], (i.e. : 100°C). 

 

When push button 1 is pressed, the setpoint value (flashing) is displayed, (i.e. : 300 °C). 

 

When push button 1 is pressed while the SP is flashing, the display shows «Cod». After 2 seconds, the current value is flashing to indicate that 
the user must enter a security code by means of the setpoint knob, to enable access to the PID parameters. 

 

The code is factory set and cannot be changed in the field. The default value is 10. 

 

If the code is entered correctly, the next message is displayed. 
If the UDC100 is a two loops model, it is possible to toggle between CH1 and CH2 by pressing push button 1. 

 

When the proportional band menu appears, this parameter can be modified by waiting until the value flashes, the value can then be altered via 
the setpoint knob. 

 

Pressing push button 1 while message "Pb" is displayed gives direct access to the next parameter (the integral time constant), and the same 
procedure above applies if the value needs to be modified. 

 

Repeat the steps detailed above to modify the derivative time constant. 

 

Used to set the output bias (manual reset) when the integral time constant parameter is set to 0. 

 

Cycle time parameter is used to adjust the time proportional output to achieve optimum control. 

 

Press push button 1 to return to the normal operating mode or wait for message "no" to appear, after a short time the UDC100 will return to 
normal PID mode. 

 

It is possible to toggle between "yes" and "no" by pressing push button 1. 
 

 

Note: 

If "yes" is selected the UDC100 will enter into manual mode just after leaving configuration mode. 

The UDC100 will remain in manual mode until "no" is reselected in configuration mode. 

 

Summary of Contents for UDC100

Page 1: ...secutive input output updates configured from 0 to 100 in 0 1 increment Setpoint low limit Configurable minimum setpoint value in 1 C increment Setpoint high limit Configurable maximum setpoint value In 1 C increment Setpoint Setpoint value used for control in 1 C increment Output power high limit Power output high limit configurable from 0 to 100 output in 0 1 increment Output power low limit Pow...

Page 2: ... of the oscillations in seconds The PID control parameters should be then calculated using the table below and then entered into the UDC100 Pb P Intervalo 100 rSt T s rtE T 6 s On off control Time s Process variable T P Determining PID parameters with ON OFF control 3 2 Output bias The output bias parameter can be used to eliminate the offset between the PV and SP when the controller is in proport...

Page 3: ... est utilisée pour réajuster la valeur de procédé à la valeur du point de consigne dans un laps de temps plus court après une perturbation dans le procédé La fonction est aussi utilisée pour limiter le dépassement de la valeur de procédé pendant le démarrage initial de ce procédé Le fonctionnement de l action dérivée est basé sur la vitesse de changement de la valeur de procédé par rapport au poin...

Page 4: ... pour régler la sortie de temps proportionnel afin d optimiser la régulation Appuyez sur le bouton 1 pour retourner en mode de fonctionnnement normal ou attendez que le message no apparaisse Après quelques instants l UDC100 retourne en mode normal PID Il est possible de passer de yes à no en appuyant sur le bouton 1 Remarque Si yes est sélectionné l UDC100 entre en mode manuel dès que l on sort du...

Page 5: ...NUELLE Remarque Le passage du mode de régulation PID au mode Station manuelle et vice versa se fait sans à coups En mode manuel le message Man clignote en alternance avec la valeur de procédé Pour régler la puissance de sortie appuyez sur le bouton correspondant à la boucle utilisée La dernière valeur de sortie est affichée cette valeur peut ensuite être réglée avec le bouton central 5 DESCRIPTION...

Page 6: ...en Sollwert einzuregeln oder bei Anfahrprozessen ein Überschwingen zu vermeiden Die Vorhaltwirkung beruht auf der Änderungsgeschwindigkeit der Abweichung zwischen Ist und Sollwert Die Vorhaltzeit ist von 0 Sekunden bis 5999 Sekunden einstellbar Ist die Vorhaltzeit auf 0 Sekunden eingestellt ist die Vorhaltwirkung ausgeschaltet Dieser Parameter ist nicht verfügbar wenn das Proportionalband auf 0 0 ...

Page 7: ...ste 1 auf yes und wieder zurück geschaltet werden Hinweis Wird yes gewählt geht der UDC100 nach dem Verlassen des Konfigurations Modus in die manuelle Betriebsart Er bleibt in der manuellen Betriebsart bis im Konfigurationsmodus no gewählt wird 3 EINSTELLUNG DER PID REGELUNG 3 1 Ermittlung der PID Parameter über die EIN AUS Regelung Stellen Sie sicher daß der Sollwert in einem Bereich liegt der mö...

Page 8: ...n und den Istwert an Zur Veränderung des Ausgangssignals drücken Sie die dem Regelkreis zugeordnete Taste Der letzte Wert des Ausgangs wird in angezeigt und kann über den Sollwert Einstellknopf verändert werden 5 BESCHREIBUNG DER PC KONFIGURATION Wahl des Regel Algorithmus Standard EIN AUS Proportionalband Nachstellzeit Vorhaltzeit Maximaler Ausgangssprung Untere Ausgangs begrenzung Obere Ausgangs...

Page 9: ...cción derivativa se utiliza para que la VP vuelva a SP más rápidamente tras una alteración del proceso Esta función también se utiliza para limitar la cantidad de sobredesviación de la VP durante la puesta en marcha inicial de un proceso El funcionamiento de la acción derivativa se basa en la velocidad de cambio de la VP con relación al SP La constante de tiempo derivativo puede configurarse de 0 ...

Page 10: ...aparece el menú de banda proporcional se puede modificar este parámetro para ello hay que esperar hasta que el valor se ponga intermitente entonces se puede modificar por medio del mando del punto de consigna Al pulsar el botón 1 mientras se visualiza el mensaje Pb se accede al siguiente parámetro la constante de tiempo integral Para su modificación se puede seguir el mismo procedimiento indicado ...

Page 11: ...superior de la primera sobredesviación y el valor inferior de la primera sobredesviación expresada en C b Sea T el tiempo de duración de las oscilaciones en segundos Los parámetros de control PID se calculan aplicando la siguiente tabla y a continuación se introducen en el UDC100 Pb P Intervalo 100 rSt T s rtE T 6 s Control on off Tiempo s T P Variable para procesar Establecimiento de los parámetr...

Page 12: ...CRIPCIÓN DEL CONFIGURADOR PC Elección del control por defecto ON OFF Banda proporcional Tiempo integral Tiempo derivativo Incremento de salida máximo Corriente de salida mínima Corriente de salida máxima Duración de salida Valor del punto de consigna Límite inferior del punto de consigna Límite superior del punto de consigna ...

Reviews: