HONEYWELL UDC120L MICRO-PRO 

UNIVERSAL LIMIT CONTROLLER PRODUCT MANUAL (51-52-25-132-EN)

 

 

 

CAUTION:

 Installation should be only performed by 

technically competent personnel. Local Regulations 
regarding electrical installation & safety must be observed. 

1. INSTALLATION 

 

Installing Option Modules

 

 

CPU PCB 

 
 

Option Module 1 

(Fixed Limit Relay)

 
 

Option Module 2 

 

 

 

Mounting Struts 

 

 

Option Module A 

 

Option Module 3 
 
 
PSU PCB 

 

To access module A, first detach the PSU and CPU boards from the front by lifting 
first the upper, and then lower mounting struts. Gently separate the boards. 

a. 

Plug the required option modules into the correct connectors, as shown below. 

b. 

Locate the module tongues in the corresponding slot on the opposite board. 

c. 

Hold the main boards together while relocating back on the mounting struts. 

d. 

Replace the instrument by aligning the CPU and PSU boards with their guides 

  

in the housing, then slowly push the instrument back into position. 

Note: Option modules are automatically detected at power up. 

 

Option Module Connectors 

Option Slot 1 

(Fixed Limit 

Relay)

 
 

Option Slot 2 

Connector

PL4A

 

 
Option Slot A 

Connectors 
PL5 & PL6 
 
 

Option Slot 3 

Connector 
PL4B

 

Panel-Mounting 

The mounting panel must be rigid, and may be up to 6.0mm 
(0.25inch) thick 
For 

n

 multiple instruments mounted side-by-side, cut-out is 

48

n

-4mm

 

 

 

 
 

Mounting Panel 

 

Instrument 

Housing 

 

Ratchets 

 

Gasket 

 

Slide mounting clamp 
over the instrument 
housing towards rear face 
of mounting panel until 
the tongues engage in 
ratchets and instrument is 
clamped in position. 
 

 

Hold instrument firmly in 
position (apply pressure 
to bezel only) 

 

CAUTION:

 

Do not remove the panel gasket; it is a seal against dust and 

moisture.

 

Rear Terminal Wiring 

 

USE COPPER CONDUCTORS (EXCEPT FOR T/C INPUT) 

Single Strand wire gauge:  Max 1.2mm (18SWG)

 

 

Actual connections required depend on the options fitted. 

 

CAUTION:

 

Check information label on housing for correct operating 

voltage before connecting supply to Power Input 
Fuse:  100 – 240V ac – 1amp anti-surge 
           24/48V ac/dc – 315mA anti-surge

 

2. SELECT 

MODE 

Select mode is used to access the configuration and operation menu functions. 
It can be accessed at any time by holding down         and pressing        . 
In select mode, press        or        to choose the required mode, press         to enter. 
An unlock code is required to prevent unauthorised entry to Configuration, & Setup 
modes. Press        or        to enter the unlock code, then press         to proceed. 

Note: At first power-up the message 

!"#"

 

$"%&

 is displayed, (see section 6). 

Access to other menus is denied until configuration mode is completed

 

Mode Upper 

Display 

Lower 

Display 

Description Default 

Unlock 

Codes

Operator 

'(#)*

+,$#*

Normal operation 

None

Set Up 

+-#(*

+,$#*

Tailor settings to the application 

./

Configuration

$"%&*

+,$#*

Configure the instrument for use 

0/

Product Info 

1%&"*

+,$#*

Check manufacturing information 

None

Note: The instrument will always return automatically to Operator mode if 
there is no key activity for 2 minutes. 

 
 

3. CONFIGURATION 

MODE 

First select Configuration mode from Select mode 

(refer to section 2).

 

Press         to scroll through the parameters, then press        or        to set the 
required value. Press         to accept the change, otherwise parameter will revert to 
previous value. To exit from Configuration mode, hold down         and press        , to 
return to Select mode. 

Note: Parameters displayed depends on how instrument has been configured. 
Refer to user guide (available from your supplier) for further details. 
Parameters marked * are repeated in Setup Mode. 

Parameter Lower 

Display 

Upper 

Display 

Adjustment range & Description

Default 

Value

Input 
Range/Type 

1%2#*

See following table for possible codes 

3$

Code  Input Type & 

Range 

Code  Input Type & 

Range 

Code  Input Type & 

Range 

bC 

B: 100 - 1824 ºC 

L

.

L: 0.0 - 537.7 ºC 

bF 

B: 211 - 3315 ºF 

L

.

L: 32.0 - 999.9 ºF 

P24F

PtRh20% vs 40%: 
32 - 3362 ºF 

CC 

C: 0 - 2320 ºC 

NC 

N: 0 - 1399 ºC 

PTC

Pt100: –199 - 800 ºC 

CF 

C: 32 - 4208 ºF 

NF 

N: 32 - 2551 ºF 

PtF

Pt100: –328 - 1472 ºF 

JC 

J:  –200 - 1200 ºC 

rC 

R: 0 - 1759 ºC 

Pt

.

C

Pt100: –128.8 - 537.7 ºC 

JF 

J:  –328 - 2192 ºF 

rF 

R: 32 - 3198 ºF 

Pt

.

F

Pt100: –199.9 - 999.9 ºF

j

.

C

J:  –128.8 - 537.7 ºC 

SC 

S: 0 - 1762 ºC 

/40/

0 - 20 mA DC 

j

.

F

J:  –199.9 - 999.9 ºF 

SF 

S: 32 - 3204 ºF 

540/

4 - 20 mA DC 

KC 

K: –240 - 1373 ºC 

tC 

T: –240 - 400 ºC 

/46/

0 - 50 mV DC 

KF 

K:  –400 - 2503 ºF 

tF 

T: –400 - 752 ºF 

./

.

6/

10 - 50 mV DC 

k

.

C

K: –128.8 - 537.7 ºC 

t

.

T: –128.8 - 400.0 ºC 

/46*

0 - 5 V DC 

K

.

F

K: –199.9 - 999.9 ºF 

t

.

T: –199.9 - 752.0 ºF 

.46*

1 - 5 V DC 

LC 

L: 0 - 762 ºC 

/4./

0 - 10 V DC 

LF 

L: 32 - 1403 ºF 

P24C

PtRh20% vs. 40%:  
0 - 1850 ºC 

04./

2 - 10 V DC 

Note: Decimal point shown in table indicates temperature resolution of 0.1°

 

Parameter Lower 

Display 

Upper 

Display 

Adjustment range & Description

Default 

Value

Scale Range 
Upper Limit 

)7,*

Scale Range Lower Limit +100 

to Range Maximum 

Range max 

(Lin=1000)

Scale Range 
Lower Limit 

),,*

Range Minimum to 

Scale Range Upper Limit -100 

Range min 

(Linear=0)

Decimal point 
position 

82"+*

/

=

XXXX, 

.

=

XXX.X, 

0

=

XX.XX, 

9

=

X.XXX

(non-temperature ranges only) 

.

Process Variable 
Offset 

'&&+*

±

Span of controller 

(

see 

CAUTION

 note at end of section

/

:1*

High Limit. 

Limit relay is energised when 

process “safe” (PV < Limit Setpoint)

Limit Action 
 

$;<,*

,"*

Low Limit. 

Limit relay is energised when 

process “safe” (PV > Limit Setpoint)

:1

Setpoint Upper 
Limit 

+27,*

Current Setpoint to Scale Range maximum

R/max

Setpoint Lower 
Limit 

+2,,*

Scale Range minimum to Current Setpoint 

R/min

24:1*

Process High Alarm  

24,"*

Process Low Alarm 

8=*

Deviation Alarm 

>?%8*

Band Alarm 

Alarm 1Type 

?,?.*

%"%=*

No alarm 

24:1

High Alarm 1 
value* 

2@?.*

Range Max

Low Alarm 1 
value* 

2,?.*

Scaled Range Minimum to 

scaled Range Maximum in display units 

Range Min

Band Alarm 1 
value* 

>?,.*

1 LSD to span from setpoint in display units

6

Dev. Alarm 1 
value* 

8?,.*

+/- Span from setpoint in display units 

6

Alarm 1 
Hysteresis* 

?:A.*

1 LSD to full span in display units 

.

Alarm 2 Type* 

?,?0

24,"*

High Alarm 2 
value* 

2@?0

Range Max 

Low Alarm 2 
value* 

2,?0

Range Min 

Band Alarm 2 
value* 

>?,0

6*

Dev. Alarm 2 
Value* 

8?,0

6*

Alarm 2 
Hysteresis* 

?:A0

Options as for alarm 1 

.*

,

Mm

#

Limit Output Relay 

?B48

Alarm 1, Direct 

?.4)

Alarm 1, Reverse 

?048

Alarm 2, Direct 

?04)

Alarm 2, Reverse 

')48

Logical Alarm 1 OR 2, Direct 

')4)

Logical Alarm 1 OR 2, Reverse 

?848

Logical Alarm 1 AND 2, Direct 

?84)

Logical Alarm 1 AND 2, Reverse 

?%48

Limit Annunciator, Direct 

?%4)

Limit Annunciator, Reverse 

?B48*

)-#+

Retransmit Limit SP Output 

Output 2 Usage 

C+=0

)-#2

Retransmit PV Output 

)-#2

 

/46*

0 to 5 V DC output 1 

/4./

0 to 10 V DC output 

04./

2 to 10 V DC output 

/40/

0 to 20 mA DC output 

Linear Output 2 
Range 

#A20

540/

4 to 20 mA DC output 

/4./*

Retransmit 
Output 2 Scale 
maximum 

)"0:

-1999 to 9999 

(display value at which output 

will be maximum) 

Range max 

Retransmit 
Output 3 Scale 
minimum 

)"0,

-1999 to 9999 

(display value at which output 

will be minimum) 

Range min 

Output 3 Usage 

C+=9

As for output 2 

?B48*

Linear Output 3 
Range 

#A29

As for output 2 

/4./*

Retransmit 
Output 3 Scale 
maximum 

)"9:

-1999 to 9999 

(display value at which output 

will be maximum) 

Range max 

Retransmit 
Output 3 Scale 
minimum 

)"9,

-1999 to 9999 

(display value at which output 

will be minimum) 

Range min 

=%?>

PV is visible in Operator mode 

Display Strategy

81D(

81+?

PV not visible in Operator mode 

=%?>

?+$E

ASCII 

Mm

>%

Modbus with no parity 

Mm

>=

Modbus with Even Parity 

Serial 
Communications
Protocol 

2)"#

Mm

>"

Modbus with Odd Parity 

Mm

>%*

.

.

0*

1.2 kbps 

0

.

5*

2.4 kbps 

5

.

F*

4.8 kbps 

G

.

H*

9.6 kbps 

Serial 
Communications 
Bit Rate 
 

>?78

.G

.

0*

19.2 kbps 

5

.

F*

Comms Address

?88)

*

1 to 255 (Modbus), 1 to 99 (ASCII) 

.*

)4

Ww

Read/Write 

Comms Write 

$"=%

)4/*

Read only 

)4

Ww

*

Configuration 
Lock Code 

$,"I

0 to 9999 

0/*

 
 

Notes: Output 1 is always a Latching Limit Relay output.  
If Option Slot A has the Digital Input module fitted, this always functions as a 
Remote Reset, duplicating the function of the Reset) key       .

 

 

As these functions cannot be changed, no Configuration menus are required. 
 

 

CAUTION:

 

Process Variable Offset can be use to modify the measured 

value to compensate for probe errors. Positive values increase the 
reading, negative values are subtracted. This parameter is effectively, 
a calibration adjustment and MUST be used with care.

 

There is no front panel indication of when this parameter is in use. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

4. SETUP 

MODE 

Note: Configuration must be completed before adjusting Setup parameters. 

First select Setup mode from Select mode 

(refer to section 2).

 The Setup LED        

will light while in Setup mode. Press         to scroll through the parameters,  
then press        or        to set the required value. 
To exit from Setup mode, hold down         and press         to return to Select mode. 

Note: Parameters displayed depends on how instrument has been configured.

 

Parameter Lower 

Display

Upper Display Adjustment 

Range & Description 

Default 

Value

Limit Setpoint value 

+2*

Scaled Range Minimum to 

scaled Range Maximum 

R/max if 

$#),

=

:1

 

R/min if 

$#),

=

,"

 

Limit Hysteresis 

:J+#*

1 LSD to full span in display units, 

on the safe side of the limit SP 

.

Input Filter Time Constant 

&1,#*

OFF or 0.5 to 100.0 secs 

(

see 

CAUTION

 note below

0

.

/

High Alarm 1 value 

2@?.

R/max

Low Alarm 1 value 

2,?.*

Scaled Range Minimum to 

scaled Range Maximum 

R/min

Deviation Alarm 1 Value 

8?,.*

±

Span from SP in display units 

6

Band Alarm 1 value 

>?,.*

1 LSD to span from setpoint 

6

Alarm 1 Hysteresis 

?:A.

1 LSD to full span in display units

.

High Alarm 2 value 

2@?0

R/max

Low Alarm 2 value 

2,?0*

Scaled Range Minimum to 

scaled Range Maximum 

R/min

Deviation Alarm 2 Value 

8?,0*

±

Span from SP in display units 

6

Band Alarm 2 value 

>?,0*

1 LSD to span from setpoint 

6

Alarm 2 Hysteresis 

?:A0

1 LSD to full span in display units

.

Setup Lock Code 

+,"I*

0 to 9999 

./

Note: Operator mode screens follow, without exiting from Setup mode

 

CAUTION:

 

An excessively large filter time could significantly delay 

detection of a limit condition. Set this value to the minimum required 
to remove noise from the process variable

 

 
 

5.  PRODUCT INFORMATION MODE 

First select Product information mode from Select mode

 (refer to section 2).

 

Press         to view each parameter. To exit from Product Information mode, 
hold down         and press         to return to Select mode. 

Note: These parameters are all read only.

 

 

Parameter Lower 

Display

Upper 

Display

Description

Input type 

E%4.

C%1*

Universal input

Option 1 type 

(fixed)

 

'2%.

),J*

Latching Limit Relay

%"%=

No option fitted

),J*

Relay output

++)*

SSR drive output

#)1*

Triac output

Option 2 module type 
fitted 

'2%0

,1%*

Linear DC voltage / current output

%"%=

No option fitted

),J*

Relay output

++)*

SSR drive output

,1%*

Linear DC voltage / current output

Option 3 module type 
fitted 

'2%9

8I05

24VDC Transmitter power supply

%"%-

No option fitted

)5F6

RS485 communications

Auxiliary Option A 
module type fitted 

'2%?

81!1

Digital Input for remote reset

Firmware type 

&KL*

Value displayed is firmware type number

Firmware issue 

EDD*

Value displayed is firmware issue number

Product Revision Level 

2<,*

Value displayed is Product Revision level

Date of manufacture 

8'

Mm

Manufacturing date code 

(mmyy)

Serial number 1 

+%.*

First four digits of serial number

Serial number 2 

+%0*

Middle four digits of serial number

Serial number 3 

+%9*

Last four digits of serial number

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

45 x 45mm 

(+0.5 /  

-0.0mm)