90
UDC 3300 Process Controller Product Manual
4/00
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
KPG*
0.10 to 10.00
PROCESS GAIN LOOP 1—This is the Gain of the
process being tuned on Loop 1. It is automatically
calculated during tuning process. This is normally a READ
only value. It should only need to be changed if the
controller fails to identify the process. In this case, set the
value to the algebraic value of PV in percent, divided by
output in percent while in the manual mode.
ATTENTION Note you must disable Accutune to change
tuning constant values from the keyboard.
SP CHAN2*
5 to 15 %
SETPOINT CHANGE LOOP 2—The minimum setpoint
change on Loop 2 that will result in re-tuning must be
configured between 5 % and 15 %.
KPG 2*
0.10 to 10.00
PROCESS GAIN LOOP 2—This is the Gain of the
process being tuned on Loop 2. It is automatically
calculated during tuning process. This is normally a READ
only value. It should only need to be changed if the
controller fails to identify the process. In this case, set the
value to the algebraic value of PV in percent, divided by
output in percent while in the manual mode.
ATTENTION Note you must disable Accutune to change
tuning constant values from the keyboard.
CRITERIA*
NORMAL
FAST
TUNING CRITERIA (SETPOINT ADAPTIVE)—Select a
criteria best suited for your process on Loop 1.
NORMAL—Original critical damping (no overshoot).
FAST—A more aggressive tuning with a minimal possible
overshoot of less than 0.5 %.
CRITERA2*
NORMAL
FAST
TUNING CRITERIA FOR LOOP 2 (SETPOINT
ADAPTIVE)—Select a criteria best suited for your process
on Loop 2.
NORMAL—Original critical damping (no overshoot).
FAST—A more aggressive tuning with a minimal possible
overshoot of less than 0.5 %.
For Example: Slightly underdamped
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......