UDC 3300 Process Controller Product Manual
4/00
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
TOT RATE
SECOND
MINUTE
HOUR
DAY
ML/DAY
TOTALIZER INTEGRATION RATE—Determines the rate
at which the Totalizer is updated.
SECOND —Engineering units per second
MINUTE—Engineering units per minute
HOUR—Engineering units per hour
DAY —Engineering units per day
MIL/DAY—Millions of units per day
ATTENTION The source of the Totalizer is averaged
over the sample and update rates. For example, since the
loop cycle speed is six per second, then with the Totalizer
Rate set at once per minute, the source is averaged six
times per second and the Totalizer value is updated with
this average value ÷ 60 once per second.
NOTE 1:
Does not apply to Three Position Step Control.
NOTE 2.
If the calculated value of the quantity under the square root sign decreases to a value less than 0.010, the
calculation will become linear as the calculated value decreases below 0.010.
*Where: K = 0.001 to 1000 (configurable)
Calc Hi and Calc Lo are configurable over a range of –999 to 9999
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......