UDC 3300 Process Controller Product Manual
4/00
Lower Display
Prompt
Upper Display
Range of Setting
or Selection
Parameter
Definition
AUX OUT
DEV
DEVIATION (PROCESS VARIABLE MINUS
SETPOINT)—Represents –100 % to +100 % of the
selected PV span in engineering units.
FOR EXAMPLE:
Type T Thermocouple
PV range = –300 °F to +700 °F
PV span = 1000 °F
Deviation Range = –1000 °F to +1000 °F
If PV = 500 °F
and SP = 650 °F
then Deviation Display = –150 °F
Auxiliary Output = 42.5 %
When Deviation is selected, only one operating parameter
will be entered. This value represents the deviation level
that will produce 20 mA (100 %) output. Zero deviation will
produce a center scale (12 mA or 50 %) output. A
negative deviation equal in magnitude to the auxiliary
output high value will produce a low end (4 mA or 0 %)
output.
OUTPUT
OUTPUT—Represents the displayed controller Loop 1
output in percent (%). Cannot be used with
3 Position Step Control.
SP
SETPOINT—Represents the Loop1 value of the setpoint
in units of PV.
LSP 1
LOCAL SETPOINT ONE—Auxiliary output represents
Loop1 local setpoint one regardless of active setpoint.
IN AL1
INPUT ALGORITHM 1 OUTPUT—Represents the output
from input algorithm 1.
IN AL2
INPUT ALGORITHM 2 OUTPUT—Represents the output
from input algorithm 2.
PV2
PROCESS VARIABLE 2—Represents the value of the
Process Variable for Loop 2.
DEV 2
DEVIATION 2 (PROCESS VARIABLE MINUS
SETPOINT)—Represents –100 % to +100 % of the
selected PV span in engineering units for Loop 2.
When Deviation is selected, only one operating parameter
will be entered. This value represents the deviation level
that will produce 20 mA (100 %) output. Zero deviation will
produce a center scale (12 mA or 50 %) output. A
negative deviation equal in magnitude to the auxiliary
output high value will produce a low end (4 mA or 0 %)
output.
OUTPT2
OUTPUT 2—Represents the displayed controller output in
percent (%) for Loop 2.
SP L2
SETPOINT 2—Represents the value of the setpoint in
units of PV for Loop 2.
LSP1 2
LOCAL SETPOINT 2—Represents the value of local
setpoint #1 in units of PV for Loop 2.
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......