220
UDC 3300 Process Controller Product Manual
4/00
7.2 Minimum and Maximum Range Values
Select the range values
You should calibrate the controller for the minimum (0 %) and maximum
(100 %) range values of your particular sensor. If you have a two-input
controller, calibrate each input separately.
Select the Voltage or Resistance equivalent for 0 % and 100 % range
values from Table 7-1. Use these value when calibrating your controller.
Table 7-1
Voltage and Resistance Equivalents for 0 % and 100 % Range Values
PV Input Range
Range Values
Sensor Type
° F
° C
0 %
100 %
Thermocouples
B
0 to 3300
–18 to 1816
–0.100 mV
13.769 mV
E
-454 to 1832
–270 to 1000
–9.835 mV
76.373 mV
E (low)
-200 to 1100
–129 to 593
–6.472 mV
44.455 mV
J
0 to 1600
–18 to 871
–0.886 mV
50.060 mV
J (low)
20 to 770
–7 to 410
–0.334 mV
22.400 mV
K
0 to 2400
–18 to 1816
–0.692 mV
52.952 mV
K (low)
–20 to 1000
–29 to 538
–1.114 mV
22.255 mV
NiNiMoly (NNM68)
32 to 2500
0 to 1371
0.000 mV
71.330 mV
NiNiMoly (low)
32 to 1260
0 to 682
0.000 mV
31.820 mV
NiMo-NiCo (NM90)
32 to 2500
0 to 1371
0.000 mV
71.773 mV
NiMo-NiCo (low)
32 to 1260
0 to 682
0.000 mV
31.825 mV
Nicrosil Nisil (Nic)
0 to 2372
–18 to 1300
–0.461 mV
47.513 mV
R
0 to 3100
–18 to 1704
–0.090 mV
20.281 mV
S
0 to 3100
–18 to 1704
–0.092 mV
17.998 mV
T
-300 to 700
–184 to 371
–5.341 mV
19.097 mV
T (low)
-200 to 500
–129 to 260
–4.149 mV
12.574 mV
W5W26
0 to 4200
–18 to 2315
–0.234 mV
37.075 mV
W5W26 (low)
0 to 2240
–18 to 1227
–0.234 mV
22.283 mV
Honeywell Radiamatic
Type RH
Type RI*
0 to 3400
0 to 9999 max.
–18 to 1871
–18 to 9999 max.
0.00 mV
0.00 mV
57.12 mV
60.08 mV
RTD
(IEC Alpha=0.00385)
100 ohms
100 ohms (low)
200 ohms
500 ohms
-300 to 1200
-300 to 300
-300 to 1200
-300 to 1200
–184 to 649
–184 to 149
–184 to 649
–184 to 649
25.18 ohms
25.18 ohms
50.36 ohms
125.90 ohms
329.13 ohms
156.90 ohms
658.26 ohms
1645.65 ohms
Linear
Milliamps
4 to 20 mA
0 to 20 mA
4.00 mA
0.00 mA
20.00 mA
20.00 mA
Millivolts
0 to 10 mV
0 to 50 mV
0.00 mV
0.00 mV
10.00 mV
50.00 mV
Volts
1 to 5 Volts
0 to 5 Volts
0 to 10 Volts
1.00 Volts
0.00 Volts
0.00 Volts
5.00 Volts
5.00 Volts
10.00 Volts
Carbon
0 to 1250 mV
0.00 mV
1250 mV
Oxygen
–30 to 510 mV
–30.00 mV
510.00 mV
*User must enter the range manually per RI type and application.
ATTENTION
Thermocouple voltages are for a reference junction temperature of 32 °F (0 °C).
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......