46
UDC 3300 Process Controller Product Manual
4/00
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
RECYCLES
Number of Program
Recycles
0 to 99 recycles
––
Section
4.4
SOAK DEV
Guaranteed Soak Deviation
Value
0 to 99
The number selected will be the PV
value (in engineering units) above or
below the setpoint outside of which
the timer halts.
––
PROG END
Program Termination State
LASTSP (Hold at last setpoint in the
program)
F SAFE (Manual mode/Failsafe
output)
––
STATE
Program State at Program
End
DISABL
HOLD
––
KEYRESET
Reset/Rerun SP Program
DISABL
TOBEGN
RERUN
DISABL
HOTSTART
Hot Start
DISABL
ENABL
DISABL
SEG1RAMP or
SEG1RATE
Segment #1 Ramp Time or
Segment #1 Ramp Rate
0-99 hours.0-59 minutes
Engineering units/minute or
Engineering units/hour
Select TIME, EU/MIN, or EU/HR at
prompt RAMPUNIT. All ramps will
use the same selection.
––
SEG2 SP
Segment #2 Soak Setpoint
Value
Within the Setpoint limits
––
SEG2TIME
Segment #2 Soak Duration
0-99 hours.0-59 minutes
––
SEG3RAMP or
SEG3RATE
SEG4 SP
SEG4TIME
SEG5RAMP or
SEG5RATE
SEG6 SP
SEG6TIME
SEG7RAMP or
SEG7RATE
SEG8 SP
SEG8TIME
SEG9RAMP or
SEG9RATE
SG10 SP
SG10TIME
SG11RAMP or
SG11RATE
SG12 SP
SG12TIME
Same as above
Selections are same as above.
––
*Requires SP Programming option
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......