UDC 3300 Process Controller Product Manual
57
3.14
Input 3 Parameters Set Up Group
Introduction
This data deals with various parameters required to configure Input 3.
Function prompts
Table 3-11 lists all the function prompts in the Input 3 Set Up group.
Table 3-11
Input 3 Group Function
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
IN3 TYPE*
Input 3 Actuation Type
DISABL
0-20mA
4-20mA
0-5 V
1-5 V
DISABL
Section
4.10
XMITTER3
Transmitter Characterization
B TC
S TC
E TC H
T TC H
E TC L
T TC L
J TC H
W TC H
J TC L
W TC L
K TC H
100 PT
K TC L
100 LO
NNM H
200 PT
NNM L
500 PT
NM90 H
RAD RH
NM90 L
RAD RI
NIC TC
LINEAR
R TC
SQROOT
LINEAR
IN3 HI
Input 3 High Range Value
(Linear Inputs only)
–999. to 9999. floating
(in engineering units)
1000
IN3 LO
Input 3 Low Range Value
(Linear Inputs only)
–999. to 9999. floating
(in engineering units)
0
RATIO 3
Input 3 Ratio
–20.00 to 20.00
1.000
BIAS IN3
Input 3 Bias
–999. to 9999.
(in engineering units)
0
FILTER 3
Input 3 Filter
0 to 120 seconds
0
*Not available on DC330B
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......