58
UDC 3300 Process Controller Product Manual
4/00
3.15
Loop 1 Control Parameters Set Up Group
Introduction
The functions listed in this group define how the Single Loop process
controller or Loop 1 of a Two Loop process controller will control the
process.
Function prompts
Table 3-12 lists all the function prompts in the Control Set Up group.
Table 3-12
Control Group Function Prompts
Function Prompt
Lower Display
Function
Name
Selections or
Range of Setting
Upper Display
Factory
Setting
Refer
to
PV SOURC
Process Variable Source
INP 1
IN AL1
INP 3
INP 2
IN AL2
INP 1
Section
4.11
PID SETS
Tuning Parameter Sets
1 ONLY
2KEYBD
2PV SW
2SP SW
GAIN S (Gain scheduling
automatically disables Accutune for
this loop)
1 ONLY
SW VALUE
Automatic Switchover Value
Value in engineering units within PV
or SP range limits
0.00
LSP’S
Local Setpoint Source
1 ONLY
TWO
THREE (Selection automatically
disables RSP SRC)
1 ONLY
RSP SRC
Remote Setpoint Source
NONE
IN AL1
INP 3
INP 2
IN AL2
NONE
AUTOBIAS
Automatic Bias
ENABLE
DISABL
DISABL
SP TRACK
Local Setpoint Tracking
NONE
PV
RSP
NONE
PWR MODE
Power Up Mode Recall
MANUAL
A LSP
A RSP
AM SP
AM LSP
MANUAL
PWR OUT
TPSC Output Start-up Mode
LAST
F’SAFE
LAST
SP HiLIM
Setpoint High Limit
0 to 100 % of span input in
engineering units
1000
SP LoLIM
Setpoint Low Limit
0 to 100 % of span input in
engineering units
0
ACTION
Control Output Direction
DIRECT
REVRSE
REVRSE
Summary of Contents for UDC3300
Page 1: ...Sensing and Control UDC 3300 Universal Digital Controller Product Manual 51 52 25 55D 4 00 ...
Page 12: ...xii UDC 3300 Controller Product Manual 4 00 ...
Page 18: ...6 UDC 3300 Controller Product Manual 4 00 ...
Page 90: ...78 UDC 3300 Process Controller Product Manual 4 00 ...
Page 230: ...218 UDC 3300 Controller Product Manual 4 00 ...
Page 254: ...242 UDC 3300 Controller Product Manual 4 00 ...
Page 292: ...Index 280 UDC 3300 Controller Product Manual 4 00 ...
Page 293: ......