Configuration
3/07
UDC3500 Universal Digital Controller Product Manual
97
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
Σ
RESET?
NO
YES
TOTALIZER RESET
—This prompt appears only if
the totalizer is unlocked.
NO
—No Reset
YES
—Resets the Totalizer value on next
Function
Function
Function
key press.
TOT RATE
SECOND
MINUTE
HOUR
DAY
ML/DAY
TOTALIZER INTEGRATION RATE
—Determines
the rate at which the Totalizer is updated.
SECOND
—Engineering units per second
MINUTE
—Engineering units per minute
HOUR
—Engineering units per hour
DAY
—Engineering units per day
MIL/DAY
—Millions of units per day
ATTENTION
The source of the Totalizer is
averaged over the sample and update rates. For
example, as the loop cycle speed is six per second,
then with the Totalizer Rate set at once per minute,
the source is averaged six times per second and the
Totalizer value is updated with this average value ÷
60 once per second.
POLYNOM
DISABLE
INPUT 1
INPUT 2
INPUT 3
INPUT 4
INPUT 5
POLYNOMIAL EQUATION
—A fifth order Polynomial
Equation can be used on any one of the five Analog
Inputs.
The equation is in the form:
Y = C0 + C1 X + C2 * 10-1 X2 + C3 * 10-3 X3 + C4 * 10-5 X4 + C5 * 10-7 X5
Where:
X
is the value of the input in % of span
C0 is a value between –99.99 to +99.99
C1 – C5 are values between –9.999 to +9.999
Ratio and Bias can be applied on the “Y” output term as
follows:
Calculated “Y” Value = Y * Input X Ratio + Input X Bias
After the Polynomial is enabled, refer to the prompts listed
below and enter the coefficients.
C0 VALUE
–99.99 to 99.99
POLYNOMIAL COEFFICIENT C0
C1 VALUE
–9.999 to 9.999
POLYNOMIAL COEFFICIENT C1
C2 X 10 –1
–9.999 to 9.999
POLYNOMIAL COEFFICIENT C2
C3 X 10 –3
–9.999 to 9.999
POLYNOMIAL COEFFICIENT C3
C4 X 10 –5
–9.999 to 9.999
POLYNOMIAL COEFFICIENT C4
C5 X 10 –7
–9.999 to 9.999
POLYNOMIAL COEFFICIENT C5