Configuration
138
UDC3500 Universal Digital Controller Product Manual
3/07
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
A RSP
AUTOMATIC MODE, LAST RSP
—At power-up, the
controller will use automatic mode with the last
remote setpoint used before power down displayed.
AM SP
LAST MODE/LAST SETPOINT
—At power-up, the
controller will use the last mode and last Setpoint
used before power down.
AM LSP
LAST MODE/LAST LOCAL SETPOINT
—At power-
up, the controller will use the last mode and last
Local Setpoint used before power down.
PWR OUT
For Three Position
Step Control Only
THREE POSITION CONTROL STEP OUTPUT
START-UP MODE
—This selection determines what
position the motor will be in when powered up or in
the failsafe position.
(Note 3)
LAST
LAST OUTPUT
—At power-up in automatic mode,
the motor position will be the last one prior to power
down. When the unit goes into FAILSAFE, it will stay
in automatic mode. The motor will
not
be driven to
the configured failsafe position.
F’SAFE
FAILSAFE OUTPUT
—At power-up in manual mode,
the motor will be driven to either the 0 % or 100 %
output position, whichever is selected at prompt
FAILSAFE. For Burnout/None, when the unit goes
into FAILSAFE, it will go to manual mode. The motor
will be driven to the configured failsafe position.
SP HiLIM
NOTE 5
SETPOINT HIGH LIMIT *
—This selection prevents
the local and remote setpoints from going above the
value selected here. The setting must be equal or
less than the upper range of the inputs.
SP LoLIM
NOTE 5
SETPOINT LOW LIMIT *
—This selection prevents
the local and remote setpoints from going below the
value selected here. The setting must be equal or
greater than the lower range of the inputs.
* The local setpoint will automatically adjust itself to be within the setpoint limit range. For example, if SP
= 1500 and SP HiLIM is changed to 1200, then the SP will be changed to 1200.
ACTION
CONTROL OUTPUT DIRECTION
—Select direct or
reverse output action.
DIRECT
DIRECT ACTING CONTROL
—The controller’s
output
increases
as the process variable increases.
REVERSE
REVERSE ACTING CONTROL
—The controller’s
output
decreases
as the process variable increases.