Configuration
162
UDC3500 Universal Digital Controller Product Manual
3/07
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
BAUD
4800
9600
19200
38400
BAUD RATE
—Communications transmission speed
in bits per second. This value is used for both RS-
485 and IR Communications, but for IR
Communications, values below 19200 baud are
interpreted as being 19200 baud.
4800 BAUD
9600 BAUD
19200 BAUD
38400 BAUD
TX DELAY
1 to 500 milliseconds
TX DELAY
—Configurable response-delay timer
allows you to force the instrument to delay its
response for a time period of from 1 to 500
milliseconds compatible with the host system
hardware/software.
WS FLOAT
FP_B
FP_BB
FP_L
FP_LB
Defines word/byte order of floating point data for
communications. Byte values:
0 1 2 3
seeeeeee emmmmmmm mmmmmmmm mmmmmmmm
Where:
s = sign, e = exponent, m = mantissa bit
0 1 2 3
1 0 3 2
3 2 1 0
2 3 0 1
SHED ENAB
DISABLE
ENABLE
SHED ENABLE
—Disables/enables shed
functionality.
SHEDTIME
0 to 255
SHED TIME
—The number that represents how
many sample periods there will be before the
controller sheds from communications. A setting of 0
means No Shed (Unit remains in Slave Mode),
1 means 1/3 seconds delay before shed and each
increment adds an additional 1/3 seconds.
ATTENTION
If ComSTATE is set to MODBUS and
if SHEDENAB is set to DISABLE, then Shed Time
will not be configurable.
SHEDMODE
SHED CONTROLLER MODE AND OUTPUT
LEVEL
—Determines the mode of local control you
want when the controller is shed from the
communications link.
LAST
LAST
—SAME MODE
The controller will return to the same mode (manual
or automatic) that it had before shed.