Configuration
174
UDC3500 Universal Digital Controller Product Manual
3/07
3.26 Maintenance Set Up Group
Introduction
The Maintenance group prompts are part of the Healthwatch feature. These prompts let
you count and time the activity of discrete events such as relays, alarms, control modes
and others, to keep track of maintenance needs.
Function Prompts
Table 3-26
MAINTENANCE Group Function Prompts
Function Prompt
Lower Display
Selections or
Range of Setting
Upper Display
Parameter
Definition
TIME1
DISABLE
LASTRES
AL1 SP1
AL1 SP2
AL2 SP1
AL2 SP2
AL3 SP1
AL3 SP2
AL4 SP1
AL4 SP2
TIMER 1
—The timer tracks the elapsed time of the
selected event.
DISABLE
—Disables the timer.
LAST RESET
—Time elapsed since the last reset.
ALARM 1 SETPOINT 1
—Cumulative time Alarm 1
Setpoint 1 was activated.
ALARM 1 SETPOINT 2
—Cumulative time Alarm 1
Setpoint 2 was activated.
ALARM 2 SETPOINT 1
—Cumulative time Alarm 2
Setpoint 1 was activated.
ALARM 2 SETPOINT 2
—Cumulative time Alarm 2
Setpoint 2 was activated.
ALARM 3 SETPOINT 1
—Cumulative time Alarm 3
Setpoint 1 was activated.
ALARM 3 SETPOINT 2
—Cumulative time Alarm 3
Setpoint 2 was activated.
ALARM 4 SETPOINT 1
—Cumulative time Alarm 4
Setpoint 1 was activated.
ALARM 4 SETPOINT 2
—Cumulative time Alarm 4
Setpoint 2 was activated.
MANUAL
GUAR SK
SOOTNG
DIGIN1
DIGIN2
DIGIN3
DIGIN4
MANUAL2
LOOP 1 MANUAL
—Cumulative time Loop 1 was in
Manual.
GUARANTEED SOAK
—Cumulative time the
process was outside the guaranteed soak band.
SOOTING
—Cumulative time process was in sooting
state
DIGITAL INPUT1
—Cumulative time Digital Input 1
was closed
DIGITAL INPUT 2
—Cumulative time Digital Input 2
was closed
DIGITAL INPUT3
—Cumulative time Digital Input 3
was closed
DIGITAL INPUT 4
—Cumulative time Digital Input 4
was closed
LOOP 2 MANUAL
—Cumulative time Loop 2 was in
Manual.