Monitoring and Operating the Controller
228
UDC3500 Universal Digital Controller Product Manual
3/07
Step
Operation
Press
Result
3
Select PD +
Manual Reset
Function
or
To select
PD+MR
— PD + Manual Reset
4
Select Control
Set-up Group
Setup
Until you see:
Upper Display
=
SET
Lower Display
=
CONTROL
5
Select PID SETS
Func
Loop 1/2
Until you see:
Upper Display
=
(available selections)
Lower Display
=
PID SETS
6
Select PID SETS
Function
or
To select
2KEYBD
—2 sets, keyboard selectable
7
Select LSP’S
Func
Loop 1/2
Until you see:
Upper Display
=
(available selections)
Lower Display
=
LSP’S
8
Select LSP’S
Function
or
To select
TWO
—Two LSP’s
9
Select SP TRACK
Func
Loop 1/2
Until you see:
Upper Display
=
(available selections)
Lower Display
=
SP TRACK
10
Select SP TRACK
Function
or
To select
NONE
—No SP Tracking
11
Select Tuning
Set-up Group
Setup
Until you see:
Upper Display
=
SET
Lower Display
=
TUNING
12
Select Manual
Reset Value
Func
Loop 1/2
Until you see:
Upper Display
=
(available selections)
Lower Display
=
MAN RSET
13
Configure Manual
Reset Value
or
To configure:
0
— Manual Reset Value
A Manual Reset of 0 is for no output bias and requires that
LSP2 = 0 % of the Setpoint Range. If bias is required, set
the Manual Reset value to equal the desired output bias
value.
14
Select Algorithm
Set-up Group
Setup
Until you see:
Upper Display
=
SET
Lower Display
=
ALGORTHM
15
Select Control
Algorithm
Func
Loop 1/2
Until you see:
Upper Display
=
(available selections)
Lower Display
=
CONT ALG
16
Select PID A
or
To select:
PID A
— PID A
This is defining the back-up control algorithm.