Monitoring and Operating the Controller
250
UDC3500 Universal Digital Controller Product Manual
3/07
Ramp/soak profile example
Before you perform the actual configuration, it is recommended that you draw a
Ramp/Soak profile in the space provided for each of the “
Program Record Sheets
” and
fill in the associated information in the associated Tables. An example of a Ramp-Soak
Profile is shown in Figure 4-7 and Table 4-31. Start setpoint is at 200 degrees F.
500
400
200
300
°
Time/Hours
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
SEG 2
SEG 3
SEG 4
SEG 5
SEG 6
SEG 7
SEG 8
SEG 9
SG 10
SG 11
SG 12
SEG 1
F
2076
5
Setpoint
Figure 4-7 Ramp/Soak Profile Example
Table 4-31 Ramp/Soak Profile Example (Using 12 Segments)
Prompt
Function
Segment
Value
Prompt
Function
Segment
Value
STRT SEG
Start Seg.
1
SEG4 SP
Soak SP
4
400
END SEG
End Seg.
12
SEG4TIME
Soak Time
4
1 hr.
RAMP UNIT
Engr. Unit for
Ramp
TIME
SEG5RAMP
Ramp Time
5
1 hr:30 min.
RECYCLES
Number of
Recycles
2
SEG6 SP
Soak SP
6
250
SOAK DEV
Deviation
Value
0
SEG6TIME
Soak Time
6
3 hr:0 min.
PROG END
Controller
Status
LAST
SP
SEG7RAMP
Ramp Time
7
2 hr:30 min.
STATE
Controller
State at end
HOLD
SEG8 SP
Soak SP
8
500
KEYRESET
Reset SP
Program
DISABLE
SEG8TIME
Soak Time
8
0 hr:30 min.
POWER UP
Program
Status at
Power up
ABORT
SEG9RAMP
Ramp Time
9
0
HOTSTART
PV Hot Start
DISABLE
SG10 SP
Soak SP
10
400
SEG1RAMP
Ramp Time
1
1 hr.
SG10 TIME
Soak Time
10
0 hr:30 min.
SEG2 SP
Soak SP
2
300
SG11RAMP
Ramp Time
11
3 hr:30 min.
SEG2TIME
Soak Time
2
1 hr:30 min.
SG12 SP
Soak SP
12
200
SEG3RAMP
Ramp Time
3
1 hr.
SG12TIME
Soak Time
12
0 hr:30 min.