Troubleshooting/Service
332
UDC3500 Universal Digital Controller Product Manual
3/07
7.8 Restoring Factory Configuration
Introduction
This procedure restores the configuration of the instrument back to the Factory Settings
per Section 3.31.
ATTENTION
Restoring the factory configuration overwrites all user-entered configuration changes. This
procedure cannot be undone; it is a one-way process.
Table 7-16 explains how to restore Factory Configuration.
Table 7-16 Restoring Factory Configuration
Step
What to do
1
Turn off the power to the instrument for at least five seconds.
2
Turn the power back on and simultaneously press the
Func-Loop 1/2
and
keys. This must be done while “TEST DONE” is being displayed.
3
If step 2 was performed correctly, the instrument will now display “UDC”
[Upper] “UPDATE” [Lower].
4
Press the
Func-Loop 1/2
Key. The instrument will now display “DIS” [Upper]
“RESTORE” [Lower].
5
Press the
key. The instrument will now display “CONFIG” [Upper]
“RESTORE” [Lower].
6
Press the
Func-Loop 1/2
Key. The instrument will now display “DOING”
[Upper] “RESTORE” [Lower].
7
When the instrument finishes the restore operation, it automatically resets
itself and restarts in the product mode. The instrument configuration will
now be the same as it was when the instrument left the factory and all user-
entered configurations since that time have been overwritten.