Modbus Read, Write and Override Parameters plus Exception Codes
356
UDC3500 Universal Digital Controller Product Manual
3/07
Table 10-7.1 Shed Timer Reset
Parameter
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Description
ID
Hex
Decimal
Shed Timer
Reset Loop1
127
007F
127
FP
W
Exit Slave Mode
Shed Timer
Reset Loop2
127
017F
383
FP
W
Exit Slave Mode
Associated Parameters
Refer to Table 10-8 for the codes to display or change any of the parameters associated
with the computer setpoint on loop 1.
Table 10-8 Computer Setpoint Associated Parameters for Loop 1
Parameter
Register Address
Description
ID
Hex
Decimal
Setpoint Limits
7,8
0007, 0008
007, 008
Local Setpoint #1
39
0027
039
Local Setpoint #2
53
0035
053
Local Setpoint #3
116
0074
116
Local Setpoint #4
112
0070
112
Local Setpoint Selection
173
00AD
173
Computer Setpoint Ratio
90
005A
90
Computer Setpoint Bias
91
005B
91
Shed Timer Reset
127
007F
127
Summary of Contents for UDC3500