Modbus Read, Write and Override Parameters plus Exception Codes
358
UDC3500 Universal Digital Controller Product Manual
3/07
10.7 Configuration Parameters
Overview
Listed on the next pages are the identifying codes for the parameters in the various Set-up
Groups in this instrument. Most of the parameters are configurable through the hosts.
Some are Read Only and are indicated as such and cannot be changed.
Reading or Writing
Do a Read or Write, depending on your requirements, using the identifying code and
format code listed in the tables. The range or selection available for each range is listed in
the tables.
10.7.1
Tuning Loop 1
Table 10-10 lists all the register addresses and ranges or selections for the function
parameters in the Set-up Group – Tuning Loop 1.
Table 10-10 Set-up Group – Tuning Loop 1
Parameter
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Description
ID
Hex
Decimal
Gain #1 or PB
Note 1
1
0001
001
FP
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
Rate #1
Note 1
2
0002
002
FP
R/W
0.00 to 10.00
Reset #1
Note 1
3
0003
003
FP
R/W
0.02 to 50.00
Manual Reset
13
000D
013
FP
R/W
–100 to +100
Gain #2 or PB #2
Note 1
4
0004
004
FP
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
Rate #2
Note 1
5
0005
005
FP
R/W
0.00 to 10.00
Reset #2
Note 1
6
0006
006
FP
R/W
0.02 to 50.00
Gain #3 or PB #3
Note 1
1
4001
16385
FP
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
Rate #3
Note 1
2
4002
16386
FP
R/W
0.00 to 10.00
Reset #3
Note 1
3
4003
16387
FP
R/W
0.02 to 50.00
Gain #4 or PB #4
Note 1
4
4004
16388
FP
R/W
0.001 to 1000 Gain
0.1 to 9999 PB