Modbus Read, Write and Override Parameters plus Exception Codes
360
UDC3500 Universal Digital Controller Product Manual
3/07
10.7.2 Tuning
Loop2
Table 10-11 lists all the register addresses and ranges or selections for the function
parameters in the Set-up Group – Tuning Loop 2.
Table 10-11 Set-up Group – Tuning Loop 2
Parameter
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Description
ID
Hex
Decimal
Gain #5 or PB
Note 1
1
0101
257
FP
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
Rate #5
Note 1
2
0102
258
FP
R/W
0.00 to 10.00
Reset #5
Note 1
3
0103
259
FP
R/W
0.02 to 50.00
Manual Reset
13
010D
269
FP
R/W
-100 to 100
Gain #6 or PB
Note 1
4
0104
260
FP
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
Rate #6
Note 1
5
0105
261
FP
R/W
0.00 to 10.00
Reset #6
Note 1
6
0106
262
FP
R/W
0.02 to 50.00
Gain #7 or PB
Note 1
23
0117
279
FP
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
Rate #7
Note 1
24
0118
280
FP
R/W
0.00 to 10.00
Reset #7
Note 1
25
0119
281
FP
R/W
0.02 to 50.00
Gain #8 or PB
Note 1
26
011A
282
FP
R/W
0.001 to 1000 Gain
0.1 to 9999 PB
Rate #8
Note 1
27
011B
283
FP
R/W
0.00 to 10.00
Reset #8
Note 1
28
011C
284
FP
R/W
0.02 to 50.00
Cycle Time #5
21
0115
277
FP
R/W
1 to 120 seconds
Cycle Time #6
22
0116
278
FP
R/W
1 to 120 seconds